EBL128 Operating Instructions V1.1.x
14
5
LED indicators and push buttons
LEDs and push buttons can vary according to configuration /
convention / country / language.
See also Figure 2, page 12.
LED indicators on the Fire Brigade Panel (FBP)
LED indicator
Indicating
L1
Fire (5 red)
Blinking (0.4/0.4s)
Fire alarm (also pre-warning, heavy smoke/heat alarm & key
cabinet alarm)
3
L2
Alarms queued (2 red)
Blinking (0.4/0.4s)
More than one unit / zone have generated fire alarm.
L3
Extinguishing (red)
Output(s) activated for extinguishing equipment.
4
L4
Ventilation (yellow)
Output(s) activated for fire/smoke ventilation equipment.
L5
Fire brigade tx (red)
Output activated for Fire brigade tx (routing equipment)
and/or corresponding programmable output(s) of type routing
equipment.
4
Test of routing equipment in progress (see menu H1).
L6
Operation (green)
Power on, i.e. EBL128 is power supplied via the rectifier or
the backup battery.
(FBP push buttons on next page)
3
In the New Zealand convention also "Acknowledged alarm" (ACK).
4
L3 and L5 can
as an alternative
be programmed to indicate when a
programmable input is activated,
i.e. input trigger condition "Extinguishing
system released" and "Activated routing equipment" respectively
(e.g. L5 can
be turned on when a programmable input is activated by
an activated
routing
equipment
output).
L5 is turned on until all fire alarms are reset.