7.1
Access level 1
With the door closed,
anybody
has access to the push button "Alarms
queued" (P1) – via a circular hole in the plexiglass – to scroll / browse
through the queued alarms.
7.2
Access level 2A
When the door has been opened via the fire brigade key and the door
switch has been activated (LED "Door open" is lit),
the fire brigade
personnel
have access to the push buttons / keypad to:
(P2) Silence the buzzer in EBL128
(P3) Silence the alarm devices (sounders) in the system.
(P4) Reset fire alarm(s).
(P5) Evacuate (start the sounders).
24
(P7) Paper feed (not used in EBL128).
(P8) Access, in conjunction with a fire alarm: The
fire brigade
personnel
can use "P8" (without any access code) to get access to
the menu X1-X9, i.e. to scroll through all the fire alarms (see all
point alarms), etc.
From access level 2A, the user can logon to access level 2B and 3A
respectively. See the following chapters.