MEW01091
Rev: 3
EBL128 Operating Instructions V1.1.x
90
25.8
Re-enable all control, extinguishing, venti-
lation or alarm device outputs (H2/B8)
Disabled outputs are listed in menu H4/U1.
When all outputs have been re-enabled, the LED "Disablements" (L8)
will be turned OFF, if there are no other disablements.
When all outputs type Alarm devices have been re-enabled, the LED
"
Fault / Disablements
Alarm devices" (L13) will be turned OFF.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 78.
Scroll to menu H2.
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
Scroll to menu B8.
Re-enable all control,
ventil, exting
or alarm device outputs ACCEPT? B8
"A"
Re-enable type:
0 0=Control 1=Ventilation
1=Exting 3=Alarm devices
ACCEPT?
Press:
"
0
"=control output
"
1
"=extinguishing output
"
2
"=ventilation output
"
3
"=alarm devise output.
Press "A" to accept. LED
"Disablements" (L8) will
turned off.
If type 3 = alarm devices
are re-enabled also the
LED "
Fault /
Disablements
Alarm
devices" (L13) will be
turned off.
Press 0, 1, 2 or 3
"A"
Re-enable all control,
ventil, exting
or alarm device outputs ACCEPT? B8
Scroll or press "Return" to
menu H2. Scroll or press
"Return" to log off.
"Return"
Disable or re-enable
ACCEPT? H2