Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
EBL128 Operating Instructions V1.1.x
32
12
Evacuate, LED Test, Alert
Annunciation Acknowledge and
Disable
These functions are only valid in some conventions.
A front with the push button (P5) is required.
See also chapters "Control & Indicating Equipment", page 12 and
"LED indicators and push buttons", page 14.
12.1
Evacuate
When the push button "Evacuate" (P5) is pressed, all outputs
programmed for sounders (type Alarm devices)
28
will be collectively
turned ON steady (continuous). This is indicated by the following
information in the EBL128 display:
Evacuate in progress
The sounders will remain ON until they are turned OFF by pressing
the push button "Evacuate" (P5) again.
NOTE!
The alarm devices (sounders) will in this case be activated
steady (continuous) irrespective of the fact that the outputs can be set
to something else for fire alarm (e.g. intermittent).
12.2
LED Test
When the push button "LED Test" (P5) is pressed, all LEDs on the
front, the LCD back light and all LCD pixels are lit.
12.3
Alert Annunciation Acknowledge
The button "Alert Annunciation Acknowledge" (P5) has the same
function as the Acknowledge button on an
AA
unit 1735 / 1736.
12.4
Disable
When the push button "Disable" (P5) is pressed, all zones in fire
condition will disabled.