Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
EBL128 Operating Instructions V1.1.x
123
31.6
Activate address in alarm mode (H8/S5)
One alarm point (zone-address), not a whole zone, can be manually
activated, i.e. be set in alarm status.
NOTE!
All outputs, standard and programmable, which would have
been activated by a real fire alarm from the same alarm point, will be
activated by this "manually activated" alarm as well.
Action
Text in display
Comments
"
Access
"
According to chapter
"Access code for service
and maintenance", see
page 118.
Acknowledge SERVICE signal
ACCEPT? S1
Scroll to menu S5.
Activate address in alarm mode
ACCEPT? S5
"A"
Select zone: 00 address: 00
ACCEPT?
Write the zone and
address.
Select zone: 12 address: 45
ACCEPT?
Press "A" to accept /
activate the fire alarm.
"A"
001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01
"Alarm text for 12-45"
Normal fire alarm
presentation in the
EBL128 / FBP display.
If more alarm points have
to be set in alarm status,
press "Return" to select
another zone - address and
continue as above.
"Return"
Select zone: 00 address: 00
ACCEPT?
Write the zone and
address.
Select zone: 12 address: 34
ACCEPT?
Press "A" to accept / start
the fire alarm.
"A"
"Alarms queued"
001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01
"Alarm text for 12-45"
The LED:s "Alarms
queued" (L2) are
indicating that more than
one alarm point is in
alarm. Press the button
"Alarms queued" (P1) to
see the other alarm
002 ZONE-ADDR 12-34 LAST ZONE 12 No. 01
"Alarm text for 12-34"