Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
EBL128 Operating Instructions V1.1.x
98
"
"
Sensor: 01-03 (technical address 003)
Momentary: XX°C Min: XX°C Max: XX°C
"
"
Sensor: 01-03
Current algorithm: nnnnnn
"Return"
Start Sensor : 00-00
Write the presentation
number and/or press "A"
to accept or press
"Return" to menu U3.
"Return"
Sensor values
ACCEPT?
U3
Scroll or press "Return"
to menu H4. Scroll or
press "Return" to log off.
When scrolling the message "Please Wait….." might be shown for "a second" and "No more sensors
found in the system" (before lowest and after highest possible number respectively).
Perf. Factor
= Performance factor:
Low
(min. 0) = The detector is mounted in a "stable" environment.
High
(max. 2.55) = The detector is mounted in an "unstable" environment.
See also Planning Instructions, chapter "Performance factor".
Table showing the algorithms and the shortenings respectively:
Algorithm
Short name
(nnnnnn)
83
Normal sensitivity & Normal detection (15 s)
N-15
High sensitivity & Normal detection (15 s)
H-15
Low sensitivity & Normal detection (15 s)
L-15
84
Normal sensitivity & Slow detection (35 s)
N-35
84
High sensitivity & Slow detection (35 s)
H-35
84
Low sensitivity & Slow detection (35 s)
L-35
84
Heat algorithm, Class A1
A1
Heat algorithm, Class A2 (S)
A2
Heat algorithm, Class B (S)
B
Decision algorithm
Dec
85
Default is
N-15
and
A1
respectively.
83
If some other short name is wanted, it can be changed in Win128. Up to
six characters can be used. In the DBI (Danish) convention, up to five
characters.
84
Low sensitivity and/or slow detection (35 s) might not fulfil the EN54-7
specifications.
85
Analog multi detector 4300 only.