Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
EBL128 Operating Instructions V1.1.x
92
25.10
De-activate alert annunciation function
(H2/B10)
Normal function (1):
For alarm points / zones programmed for
A
lert
A
nnunciation (via
Win128) is normally the
AA
function enabled via a time channel, e.g.
enabled daytime (during working hours) and disabled night time.
As an alternative, the
AA
function can be continuously enabled.
Off (0)
Via this menu (H2/B10) it is possible to de-activate (disable) the
AA
function, i.e. the
AA
function will be disabled for the alarm points /
zones programmed for
A
lert
A
nnunciation in spite of the time channel
is "on" or if they are programmed to be continuously enabled.
The
AA
function will stay de-activated (disabled) until re-activated
(re-enabled) again via this menu.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 78.
Scroll to menu H2.
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
Scroll to menu B10.
De-activate alert annunciation function
ACCEPT? B10
"A"
Alert annunciation function? 1
(1 = Normal, 0 = Off) ACCEPT?
Write "0" or "1" and press
"A" to accept.
"A"
De-activate alert annunciation function
ACCEPT? B10
Scroll or press "Return" to
menu H2. Scroll or press
"Return" to log off.
NOTE!
De-activated Alert Annunciation function is
not
indicated by
LED "Disablements" (L8).
Содержание MEW01091
Страница 2: ...This page has deliberately been left blank ...
Страница 141: ...This page has deliberately been left blank ...