EBL128 Operating Instructions V1.1.x
27
8
"Silence Alarm devices"
In EBL128, on the FBP, there is a push button "Silence Alarm
devices" (P3).
If the push button "Silence Alarm devices" is pressed during a pre-
warning, a fire alarm
26
or a Co-incidence alarm, the following will
happen:
LEDs "Fire" (L1) and "Alarms queued" (L2)
27
continue to be
blinking
(0.4 / 0.4).
Activated outputs
28
, programmed for sounders (type Alarm
devices), will be silenced.
In case of a new alarm, or if the push button "Silence Alarm devices"
is pressed again, the sounders will automatically sound again and the
LEDs "Fire" and "Alarms queued" starts blinking.
NOTE!
This is also valid for Pre-warning and Co-incidence alarm.
8.1
Silence alarm devices (inside switch)
NOTE!
The functions in this chapter are valid for the New Zealand
convention only.
The button "Silence alarm devices" (P3) is called the "inside switch"
and has the following function:
The inside switch toggles between two states.
Alarm devices disabled
All programmable outputs of type "Alarm devices" are
disabled, i.e. they cannotbe activated.
Alarm devices not disabled
All programmable outputs of type "Alarm devices" enabled,
i.e. they can be activated.
If the inside switch is in its disabled state when the c.i.e. door is being
closed the buzzer will beep once and the message "
Silence switch
left active
"
will be shown in the LCD. For priority order see
chapter "The display in EBL128", page 20.
NOTE!
The inside switch has no function if the outside switch (see
below) is activated (ON).
26
In the New Zealand convention "Acknowledged alarm" (ACK) as well.
27
When more than one fire alarm is activated.
28
Including Addressable siren 3377 and Addressable sounder base 337