EBL128 Operating Instructions V1.1.x
42
*** Fire Alarm ***
ZONE-ADDR:
12-45 Time HH.MM Date MM-DD
Alarm text for 12-45
or
*** Fire Alarm ***
ZONE:
14 Time HH.MM Date MM-DD
Alarm text for zone 14
Reset
of the fire alarms, see chapter "Alarm reset", page 50.
NOTE!
1. The fire alarm presentation in the EBL128 display is for the
German (VdS) convention
only, different than described above.
The serial number for the displayed alarm is deleted and the different
fields on the top row are separated by black squares as follows (an
example):
BER-ADR 12-45 █ LETZTER BER 12 █ Nr.01
"Alarm text for 12-45"
2. The fire alarm presentation in the EBL128 display is for the
New
Zealand convention
only, different than described above.
The serial number for the displayed alarm is replaced with the
information "ALM" as follows (an example):
ALM ZONE-ADDR 13-02 LAST ZONE 13 No. 02
"Alarm text for 13-02"
If the fire alarm is acknowledged (see page 53), "ALM" will be
replaced with "ACK".
If the fire alarm or the acknowledged alarm is isolated (see page 53),
"ALM" will be replaced with "ISO".
16.2.1
Fire alarm menu (X1-X9)
During the fire alarm presentation, a special fire alarm menu can be
used. (If this menu / option is excluded (via Win128), it is a violation
to the EN54-2 standard).
Fire alarms can be displayed via this menu but it can also be used to
display faults and disablements in the system.
Alarm points, zones, control outputs and alarm devices can also be
disabled / re-enabled via this menu.
During the fire alarm presentation
press button "Access"
45
and
the
alarm text
will be replaced with the following:
45
Access code is
not
required.