EBL128 Operating Instructions V1.1.x
86
25.5
Re-enable zone (H2/B5)
Disabled zones are listed in menu H4/U1.
Re-enabling via this menu has higher priority than automatic re-
enabling.
Zones disabled via the "Encapsulation function", see chapter "Single
encapsulated reset" page 50, have to be re-enabled via this menu
before they can activate a new alarm.
Zones disabled when the "New Zealand FB Silence switch" (outside
switch) is turned OFF, have to be re-enabled via menu B5 or B6
before they can activate a new alarm.
When all zones have been re-enabled, the LED "Disablements" (L8)
will be turned OFF, if there are no other disablements.
NOTE!
Alarm points that have been individually disabled via menu
H2/B2 cannot be collectively re-enabled via this menu. They have to
be individually re-enabled.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 78.
Scroll to menu H2.
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
Scroll to menu B5.
Re-enable zone
ACCEPT? B5
"A"
Re-enable zone: 00
ACCEPT? L
If there are no zones to re-
enable, menu B5 will be
shown again.
L
=a list in
which you can scroll.
If it's the correct zone to
re-enable, press "A" to
accept. If not, scroll or
write the wanted zone and
press "A" to accept.
"A"
Re-enable zone
ACCEPT? B5
If more re-enablements
shall be done, continue like
above. If not, scroll or
press "Return" to menu
H2. Scroll or press
"Return" to log off.