Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
EBL128 Operating Instructions V1.1.x
70
Download in progress......
▪▪▪▪▪▪▪▪
When the download is completed in a correct way, the following text
message will be shown:
Download completed successfully.
Control unit will now restart
Now, an automatic warm restart will take place (see chapter "Restart",
page 74).
If the download was not completed or incorrect, the following text
message will be shown:
Checksum fault in downloaded data.
Control unit will now restart
Now, an automatic warm restart will take place (see chapter "Restart",
page 74.
After the restart another text message will be shown in the display:
FAULT: Site specific data (SSD)
Date: MM-DD Time: HH:MM
This text message means that the SSD have not been downloaded
correctly, i.e. try to download the SSD once more.
20.4
Download of Alarm texts
When a fire alarm is activated (i.e. an addressable alarm point), the
presentation number (Zone - Address) is shown on the first row in the
EBL128 display and in any ext. FBP display.
68
On the second row is
a user definable alarm text shown, if programmed. See also chapter
"Fire alarm", page 39.
Each alarm point can have a unique text message. When several
alarms are activated (in one or more zones) and only the zone numbers
are shown, each zone can have a unique text message.
Each zone line input can have a unique text message.
The alarm texts will be printed out if an ext. FBP 1826 with a printer
is connected.
All alarm texts, up to 40 alphanumeric characters each, are created and
downloaded via
Win128
. See Planning Instructions, chapter "Alarm
texts".
See also the Win128 help chapters (help topics), e.g. "Download" and
the "Display unit menu" respectively.
68
Also valid for the Ext. Presentation unit 1728 and the Alert Annunciation
units 1735 / 1736.