Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
EBL128 Operating Instructions V1.1.x
20
6
Normal operation
When EBL128 is in normal operation and in quiescent state, i.e. no
fire alarms and normally no faults, no disablements, no service signal,
no zones in test mode, no activated interlocking in / outputs and/or no
open doors, only the LED "Operation" (L6) shall be lit.
6.1
The display in EBL128
The display (LCD) will in normal operation and in quiescent state
show the following information:
YYYY-MM-DD *** EBL128 *** hh:mm:ss
User programmable information text.
Top (first) row
19
:
YYYY
= Year, e.g. 2005
MM
= Month, e.g. 02 (=February)
DD
= Day, e.g. 28
hh
= hours, e.g. 21
mm
= minutes, e.g. 45
ss
= seconds, e.g. 45
Bottom (second) row:
The information on the bottom row (40 characters) can be created via
Win128, i.e. it is user definable.
6.1.1
LCD backlight
When the information above is shown in the LCD, the backlight is
OFF.
As soon as any other information (see below) is shown in the LCD,
the backlight is turned ON.
In order to reduce the current consumption, the LCD backlight will be
turned OFF if the c.i.e. is powered only by the second power source,
i.e. the battery.
20
6.1.2
The LCD information priority order
The different type of alarms, faults, etc. listed below are described in
other parts of this document.
The LCD information priority order is as follows:
19
The information on the top row (40 characters) is included in the text file
downloaded in EBL128, i.e. the information could be different than the one
showed above.
20
In the Australian and New Zealand conventions, the LCD backlight will
not
be turned OFF even if the c.i.e. is powered only by the second power
source.
NOTE!
The way the date is
presented can be different
for different languages, e.g.:
DD-MM-YYYY
.