Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
EBL128 Operating Instructions V1.1.x
87
25.6
Re-enable zone / address (H2/B6)
Disabled alarm points (zone – address) are listed in menu H4/U1.
Re-enabling via this menu has higher priority than automatic re-
enabling.
Alarm points disabled via the "Encapsulation function", see chapter
"Single encapsulated reset" page 50, have to be re-enabled via this
menu before they can activate a new alarm.
Alarm points (zone – address) disabled when the "New Zealand FB
Silence switch" (outside switch) is turned OFF, have to be re-enabled
via menu B5 or B6 before they can activate a new alarm.
See also chapter "Perform monthly test (H1)", page 79 and chapter
"Perform ZONE TEST (test mode) (H7)", page 116.
When all alarm points have been re-enabled, the LED "Disablements"
(L8) will be turned OFF, if there are no other disablements.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 78.
Scroll to menu H2:
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
Scroll to menu B6.
Re-enable zone / address
ACCEPT? B6
"A"
Re-enable zone: 00 Address: 00
ACCEPT? L
If there are no zone -
addresses to re-enable,
menu B6 will be shown
again.
L
=a list in which
you can scroll. If it's the
correct zone - address to
re-enable, press "A" to
accept. If not, scroll or
write the wanted zone -
address and press "A" to
accept.
"A"
Re-enable zone / address
ACCEPT? B6
If more re-enablements
shall be done, continue like
above. If not, scroll or
press "Return" to menu
H2. Scroll or press
"Return" to log off.