Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
EBL128 Operating Instructions V1.1.x
97
27.3
Sensor values (H4/U3)
The very first week average sensor value is calculated within 2
minutes after SSD download & restart. During these 2 minutes, fire
alarm from analog smoke detectors are suppressed and the sensor
value "000" will be shown.
The "Performance factor" and "Min. / Max." values are updated each
night (00:00), i.e. the values shown are from the previous day.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 78.
Scroll to menu H4.
Present system status on display
ACCEPT? H4
"A"
Disablement
ACCEPT?
U1
Scroll to menu U3.
Sensor values
ACCEPT?
U3
Press "A" to accept.
"A"
Start Sensor : 00-00
Write the presentation
number and/or press "A"
to accept.
E.g: "01-01"
Depending on
the type, the
following will
be shown
(examples):
"A"
Type 4301:
This is a list in which
you can scroll or use
"
"
to see the next
information window for
the selected sensor.
Press "Return" back to
"Start Sensor...".
Scroll or write a new
presentation number or
press "Return" to menu
U3.
NOTE!
XX.X%/m
= XX.X %
obscuration per meter".
Perf. Factor: see below
this table.
nnnnnn = algorithm short
name, see separate table,
page 98.
Sensor: 01-01 (technical address 001)
Momentary: XX.X%/m Weekly: XX.X%/m
"
"
Sensor: 01-01 Min: XX.X%/m
Perf Factor: X.XX%/m Max: XX.X%/m
"
"
Sensor: 01-01
Current algorithm: nnnnnn
"A"
Type 3308/3309:
Sensor: 01-02 (technical address 002)
Momentary: XX°C Min: XX°C Max: XX°C
"
"
Sensor: 01-02
Current algorithm: nnnnnn
"A"
Type 4300:
Sensor: 01-03 (technical address 003)
Momentary: XX.X%/m Weekly: XX.X%/m
"
"
Sensor: 01-03 Min: XX.X%/m
Perf Factor: X.XX%/m Max: XX.X%/m
"
"
Sensor: 01-03
Current algorithm: nnnnnn