Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
EBL128 Operating Instructions V1.1.x
119
31.2
Acknowledge SERVICE signal (H8/S1)
See chapter "Sensors activating SERVICE signal (H4/U4)", page 100.
When a sensor (analog smoke detector) that has generated SERVICE
signal is acknowledged, the sensor will be given a default sensor value
as for a new / clean sensor, i.e.
first
replace the sensor
then
acknowledge the service signal
as soon as possible
.
The very first week average sensor value after the SERVICE signal is
acknowledged will be calculated within one hour. Thereafter a new
week average sensor value will be calculated every week.
NOTE!
If a sensor is replaced without activating service signal, it has
to be reset to the default sensor value via menu H8/S2, see chapter
"Restore weekly average to default (H8/S2)", page 120.
Action
Text in display
Comments
"Access"
According to chapter
"Access code for service
and maintenance", see
page 118.
Acknowledge SERVICE signal
ACCEPT? S1
"A"
Sensor : xx-xx (technical address xxx)
needs service L
If there are no sensors to
acknowledge, menu S1
will be shown again.
L = a list in which you can
scroll. If it is the correct
sensor to acknowledge,
press "Fault acknowledge".
If not, scroll or write the
wanted sensor and press
"Fault acknowledge"
or
press "Return" to S1.
"Fault acknowledge"
The service signal for that sensor is now acknowledged and
the next sensor will be shown in the display.
If more service signal
acknowledgements shall
be done, continue like
above. If not, press
"Return" to menu S1.
Sensor : yy-yy (technical address yyy)
needs service L
"Return"
Acknowledge SERVICE signal
ACCEPT? S1
Scroll or press "Return" to
menu H8. Scroll or press
"Return" to log off.
LED "Service" (L12) will be turned off when all sensors have been
acknowledged.