EBL128 Operating Instructions V1.1.x
106
28.2
Disconnect / Re-connect zone line input
(H5/A2)
To avoid damage on the units and EBL128 during physical connection
/ disconnection of units, it is highly recommended to have the zone
line disconnected (disabled), i.e. voltage free (dead).
Disconnected (disabled) zone line input is indicated by LED "Disable-
ments" and is listed in menu H4/U1.
Action
Text in display
Comments
"Access"
According to chapter
"Access code for service
and maintenance", see
page 104.
Disconnect / Re-connect COM loop
ACCEPT? A1
Scroll to menu A2
Disconnect / Re-connect zone line input
ACCEPT? A2
"A"
Disconnect (=0) or Re-connect (=1) zone
line input? 1 ACCEPT?
Write "0" or "1" and press
"A" to accept.
Depending on if "0" or
"1" is chosen, one of
the following will be
shown:
Disconnect zone line input 0 expansion
board 0 ACCEPT?
Write the 4580 board no.
(0-7) and the zone line
input no. (0-7). Press "A"
to accept.
Re-connect zone line input 0 expansion
board 0 ACCEPT?
Disconnect (=0) or Re-connect (=1) zone
line input? 1 ACCEPT?
Write "0" or "1" and press
"A" to accept or press
"Return" menu A1.
"A"
Disconnect / Re-connect zone line input
ACCEPT? A2
Scroll or press "Return" to
H5. Scroll or press
"Return" to log off.