EBL128 Operating Instructions V1.1.x
133
34
Annual control
The building occupier is highly recommended, once a year, to do
some tests, beside the monthly tests. To avoid the Fault tx output to
be activated, it can be disabled via menu H2/B9 (or via an open door,
se chapter "Door open", page 36.).
Regarding the fault condition, see chapters "Fault", page 54 and "Fault
messages", page 55.
NOTE!
Most faults have a time delay.
EBL128 should be tested as follows:
Perform monthly test (menu H1).
Remove the battery fuse "F2" on the main board 4556. The
following fault message is to be shown:
FAULT: Battery not connected CU
Put back the fuse and acknowledge the fault (Menu H6).
Check the manual call point glasses. Take required
measures. Use the manual call point alarm test key to
activate some fire alarms.
Check that the control outputs that should be activated really
are activated according to programmed control expressions?
Reset the fire alarms.