Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
EBL128 Operating Instructions V1.1.x
131
32.5
Re-enable interlocking output (H9/C5)
Disabled interlocking outputs are listed in menu H4/U1.
Interlocking outputs (Type = Interlocking) will be re-enabled via this
menu but not via menu H2/B7.
If "00/00" is entered,
all
interlocking outputs, disabled via "00/00" in
menu H9/C4, will be re-enabled at the same time.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 78.
Scroll to menu H9.
Interlocking outputs and inputs
ACCEPT? H9
"A"
Activated interlocking outputs/inputs
ACCEPT? C1
Scroll to menu C5.
Re-enable interlocking output
ACCEPT? C5
"A"
Re-enable interlocking output
area 00 point 00 ACCEPT?
This is a list in which you
can scroll. If there are no
disabled outputs, menu C5
will be shown again.
Press "A" (for re-enable)
or "Return" (not re-enable)
to menu C5.
"A"
or
"Return"
Re-enable interlocking output
ACCEPT? C5
Scroll or press "Return" to
menu H9. Scroll or press
"Return" to log off.