Push buttons on the Fire Brigade Panel (FBP)
Push button
Operation/function
P1
Alarms queued (black) Used, when LEDs "Alarms queued" (L2) are lit, to
scroll/browse through the queued alarms (zones).
P2
Silence buzzer
(yellow)
Used to silence the buzzer in EBL128
P3
Silence Alarm devices
(red)
5
Used to silence the sounders (i.e. to "reset" outputs for alarm
devices).
6
P4
Reset (green)
Used to reset the fire alarm(s).
7
Has to be pressed for > 0.5
sec.
P5
Evacuate (green)
8
Used to activate all the sounders (i.e. the outputs for alarm
devices).
Alert Annunciation
Acknowledge (green)
9
Used to acknowledge an Alert Annunciation alarm.
Disable (yellow)
10
Used to disables all zones in alarm state.
5
In the New Zealand convention = The "inside switch".
6
Via Win128 can be set if the alarm devices shall be continuous off /
disabled
or
re-sound for a new alarm.
7
Multiple reset
(Default): All fire alarms will be reset simultaneously.
Single encapsulated reset
: The fire alarm displayed in the LCD (first row to
the left) will be reset. When more than one fire alarm is activated (LEDs
"Alarms queued" are lit) each fire alarm has to be individually reset. The
encapsulation function is described in chapter "Single encapsulated reset",
page 50.
NOTE (1)!
When "Multiple reset" is used, encapsulated reset can be done
by pressing "Reset" (P4) and 0.1 sec. later also press "Alarms queued" (P1)
and hold them pressed for > 0.5 sec. The fire alarm displayed in the LCD
(first row to the left) will be encapsulated
or
the points in alarm status within
one zone will be encapsulated
or
the whole zone (conventional) will be
encapsulated.
NOTE (2)!
When "Single encapsulated reset" is used, you can make a
"Multiple reset" by pressing "Reset" (P4) and 0.1 sec. later also press "A" (in
the keypad) and hold them pressed for > 0.5 sec.
8
"Evacuate" is only valid in the "Belgian" and "Ukrainian" conventions.
9
"Alert Annunciation Acknowledge" is only valid in the "Czech", Bulgarian
and "Polish" conventions.
10
"Disable" is only valid in the "Australian" and New Zealand conventions.