Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
EBL128 Operating Instructions V1.1.x
120
31.3
Restore weekly average to default (H8/S2)
If a sensor (analog smoke detector) is replaced without having
generated SERVICE signal, its week average sensor value has to be
restored and set to a default value. If not, the new / clean sensor will
inherit the old sensor's value. The week average sensor value has to
be restored for each replaced sensor individually.
First
replace the
sensor
then
restore the week average sensor value
as soon as
possible
.
The very first week average sensor value after restoring will be
calculated within one hour. Thereafter a new average sensor value
will be calculated each week.
NOTE!
Authorised service personnel only, must use this menu.
Used incorrectly it can cause nuisance fire alarms from a sensor or no
fire alarm at all.
Action
Text in display
Comments
"Access"
According to chapter
"Access code for service
and maintenance", see
page 118.
Acknowledge SERVICE signal
ACCEPT? S1
Scroll to menu S2.
Restore weekly average to default
ACCEPT? S2
"A"
Enter zone-address to restore: 00-00
ACCEPT?
Write the wanted zone-
address and/or press "A" to
accept.
"A"
Restore weekly average to default
ACCEPT? S2
Scroll or press "Return" to
return to menu H8. Scroll
or press "Return" to log
off.