Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
EBL128 Operating Instructions V1.1.x
28
8.2
New Zealand FB Silence switch (outside
switch)
NOTE!
The functions in this chapter are valid for the New Zealand
convention only.
The "
New Zealand FB Silence switch
" is called the "outside switch"
since it is placed outside the c.i.e. The outside switch is a key switch
and connected to a programmable input with the trigger condition
"New Zealand FB Silence switch".
The outside switch can be in two states.
The outside switch is turned ON
(i.e. from not activated to activated
state).
All programmable outputs of type "Alarm devices" are
disabled, i.e. they cannotbe activated. The "inside switch" (se
above) has no function.
LED:s "Fire" (on the front) changes from blinking to steady
(continuous).
29
The c.i.e. built-in buzzer is silenced.
A fault is generated
30
:
"
FAULT: FB Silence switch
active"
.
The outside switch is turned OFF
(i.e. from activated to not
activated state).
The fault
"
FAULT: FB Silence switch active"
will be
Serviced
.
31
Any alarm point / zone in fire alarm state will automatically be
disabled / isolated. (I.e. it has to be re-enabled via menu
H2/B5-B6.)
Any alarm point / zone in fire alarm state will automatically
change state to "Isolated alarm" and in the fire alarm list
(presented in the LCD) will "
ALM
" be changed to "
ISO
".
An example:
ISO
ZONE-ADDR 12-46 LAST ZONE 12 No. 01
This is a user defined alarm text.
29
This is valid also if the fire alarm is activated after the outside switch is
turned ON.
30
Always latched, regardless of if faults are programmed to be not latched.
31
Since this fault is always latched, it has to be acknowledged via menu H6.