Disable or re-enable (H2)
A whole zone, one or more alarm points within a zone and/or control
outputs can be disabled via menus H2/B1-B3. This possibility can be
used when a temporary disablement is wanted (e.g. craftsmen working
in the premises, etc.).
A disabled alarm point will not activate Pre-warning, fire alarm or
fault.
NOTE!
When a whole zone is disabled, the addressable manual call
points will
not
be disabled.
78
When absolutely required, they can be
individually disabled (as alarm points).
Zones
01-32
can be disabled via menu H2/B1.
All
alarm points
(zone / address) can be
individually
disabled
via menu H2/B2.
All
outputs
can be
individually
disabled via menu H2/B3.
Disabled output will stay in (or return to) the normal condition
for the output respectively.
NOTE!
All
Interlocking outputs
can be
individually
disabled via
menu H9/C4.
The
COM loop
can be disabled via menu H5/A1.
A
zone line input
can be disabled via menu H5/A2.
Don't forget to re-enable
(via menus H2/B4-B9) or use automatic re-
enablement for zones and alarm points.
Disablements are indicated by LED "Disablements" (L8) and are also
shown in the display
79
. An example:
Zone 01 is disabled
More...
More…
is indicating two or more disablements.
Disablements (and faults) are indicated by a 2-sec. beep when an open
EBL128 door is being closed.
25.1
Disable zone (H2/B1)
When a whole zone is disabled, all alarm points within the zone are
disabled excluding the addressable manual call points.
78
All zones can be disabled. Disabled zones are listed in menu H4/U1.
78
This is not valid for the
VdS (German)
, Australian and New Zealand
conventions. In these conventions also the addressable manual call points
will be disabled.
79
See chapter "The display in EBL128", page 20 regarding priority order.