Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
EBL128 Operating Instructions V1.1.x
117
seconds, then the alarm point will be automatically reset.
A sensor in test mode will not be able to activate fault.
After 60 minutes
or
"Return"
"Return"
Zones in test mode: 01, 02, 03, 04
You are now out-logged
from menu H7 but the
zones are still in test mode.
NOTE! See chapter "The display in EBL128", page 20
regarding priority order.
(When required:
"Access", "code")
Scroll to menu H7,
"A"
Zone in TEST MODE:
01 02 03 04 End test: ACCEPT
Press "A" to end the test
mode.
"A"
Perform ZONE TEST
ACCEPT? H7
The LED "Test mode" is
turned OFF.
If more zones are to be
tested, continue as above.
If not, scroll or press
"Return" to log off.
NOTE!
If an alarm point (e.g. a manual call point) is in alarm state
when the test mode is ended, there will not be a fire alarm activated.
Instead the alarm point will be disabled (the "encapsulation function")
and has to be re-enabled again, see menu H2/B6.
When the "Fire door closing" function is used, the fire door will be
closed when the detectors controlling the door are tested via the test
mode.