Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
EBL128 Operating Instructions V1.1.x
105
Disconnect / Re-connect COM loop (H5/A1)
To avoid damage on the units and EBL128 during physical connection
/ disconnection of loop units, it is highly recommended to have the
loop disconnected (disabled), i.e. the loop is voltage free (dead).
Disconnected (disabled) loop is indicated by LED "Disablements" and
is listed in menu H4/U1.
NOTE!
When you disconnect and re-connect the COM loop, all the
statistics shown in menu H5/A8 will be erased and set to "0".
Action
Text in display
Comments
"Access"
According to chapter
"Access code for service
and maintenance", see
page 104.
Disconnect / Re-connect COM loop
ACCEPT? A1
"A"
Disconnect (=0) or Re-connect (=1)
COM loop? 1 ACCEPT?
E.g. "0", "A"
Disconnect / Re-connect COM loop
ACCEPT? A1
Scroll or press "Return" to
H5. Scroll or press
"Return" to log off.