Test of alarm devices (H8/S3)
The programmable outputs
97
of type "Alarm device" can be
collectively activated via this sub menu (S3), which makes it possible
to test the alarm devices without to much disturbance on site.
The test cannotbe started if fire alarm is already activated in EBL128
When the test starts, the alarm devices will sound for approx. 5
seconds, be silent for approx. 25 seconds, sound for approx. 5 seconds
and so on.
98
NOTE!
Also disabled (and silenced) alarm devices will be tested.
Action
Text in display
Comments
"
Access
"
According to chapter
"Access code for service
and maintenance", see
page 118.
Acknowledge SERVICE signal
ACCEPT? S1
Scroll to menu S3.
Test of alarm devices
ACCEPT? S3
"A"
Test of alarm devices?
ACCEPT?
Press "A" to start the test.
"A"
Test of alarm devices in progress.
End test? ACCEPT?
The test will now
continue until stopped
via this sub menu (S3)
or automatically after
one hour or if a fire
alarm is activated.
Press "A" to stop the test.
"A"
Test of alarm devices
ACCEPT? S3
Scroll or press "Return" to
return to menu H8. Scroll
or press "Return" to log
off.
97
Including Addressable siren 3377 and Addressable sounder base 3378.
98
The output activation will be steady (continuous). For the alarm devices
3377 and 3378, the tone with the highest priority level (and type "alarm
device") will be automatically selected.