background image

Siemens 

Siemens 

Siemens 

Siemens 

Siemens Industry

Industry

Industry

Industry

Industry,,,,, Inc.

 Inc.

 Inc.

 Inc.

 Inc.

Building 

Building 

Building 

Building 

Building T

TT

TTec

ec

ec

ec

echnologies Di

hnologies Di

hnologies Di

hnologies Di

hnologies Division

vision

vision

vision

vision

A6V11208372_enUS_a

INTRODUCTION

The Model HMS-SZ and HMS-DZ Manual Stations, and
their Spanish and Portuguese versions, from Siemens
Industry, Inc., are field installed addressable devices
containing advanced control panel communication
technology. This  technology,  which  provides  two-
direction communication with the control panel,
produces an Intelligent Initiating Device. The HMS-SZ/-
SE/-SP are single action; the HMS-DZ/-DE/-DP are
double action.

PROGRAMMING

Refer to Figure 1 to locate the opening on the MS cover that allows access to the
programming holes which are on the HMS printed circuit board.

To connect the HMS to the DPU Programmer/Tester,
insert the plug from the DPU cable provided with the
Programmer/Tester into the opening on the HMS as
shown in Figure 2. Because HMS devices are polarity
insensitive, the programming plug can be inserted into
the programming holes in either direction.

To prevent potential damage to the DPU DO NO

DO NO

DO NO

DO NO

DO NOT

TT

TT

connect an HMS to the DPU until at least one wire is

removed from terminals 1 or 2 of the HMS.

Follow the instructions in the DPU Manual
(P/N 315-033260) to program the HMS to the desired
address. Record the device address on the label
located on the HMS front panel. The HMS can now
be installed and wired to the system.

OPERATION

The HMS-SZ and HMS-DZ manual stations, as well as their Spanish and Portuguese
versions, operate with the FireFinder-XLS or FS-250 Control Panels via the DLC or FS-
DLC Device Loop Card.

All HMS manual station housings have a pull down lever that locks in position after
releasing a spring loaded switch. (See Figure 4.) To indicate the manual station is
activated, the pull down lever remains down and locked until the station is physically
reset.

The HMS-DZ/-DE/-DP have an additional lever labeled 

PUSH IN/EMPUJE/EMPURRE

which must be operated first.

All models are reset by opening the hinged housing cover with an Allen key and then
closing and locking the cover.

Figure 1

MS Cover

Single/Dual Action Manual Pull Station

Installation Instructions
Models HMS-SZ / HMS-DZ
Models HMS-SE / HMS-DE (Spanish versions)
Models HMS-SP / HMS-DP (Portuguese versions)

OPENING TO

PROGRAMMING

POINTS

PLUG FROM

DPU

LOCATING TAB

PROGRAMMING

POINTS

Figure 2

Connecting the DPU Plug

INSTRUCTIONS

Отзывы: