background image

MANUAL CALL POINT

TECHNICAL CHARACTERISTICS

OPERATION TEMPERATURE RANGE

RELATIVE HUMIDITY

EXTERNAL DIMENSIONS 

CONSTRUCTION MATERIALS 

TYPICAL WEIGHT

GUARANTEE 

OPERATION VOLTAGE

ALARM CURRENT 
ALARM RESISTOR

TYPE

USE

DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH

Type A

Indoor

10-30V DC

470

ohms

8

-30mA

Bayblend FR3010

IP44

o

0 to 60  C

Up to 95% 

2 years

98 x 94 x 58 mm

180gr.

GENERAL

This is an emergency fire alarm button and is used on ships. 
Use this button to manually activate the alarm system at the 
sight  of  fire.  It  is  essential  for  it  to  exist  in  cooperation  with   
other detectors.

 

Using it is very simple. All you have to do is 

push  the  see-through  plastic  cover  and  the  button 
automatically activates the alarm system.

 

In this case the see-

through plastic cover does not brake but it can be reset to it`s 
original position with the special plastic key which is included.

 

This way you can test a specific call point and maintenance the 
fire detection panel as well. It is used as a signal to evacuate 
the building in case of fire.

 

In every fire detection system it is 

essential that you place one button besides the control panel 
and the rest mainly in corridors and exits of the building. 

CONNECTIONS

Inside the button there are four special terminal blocks 
with indications IN and OUT used to fasten the cables. 
The button is connected in parallel with other buttons 
or  detectors  or  can  be  connected  on  a  zone  of  the 
control panel by itself.

 

If the last device installed on a 

zone is

 

the button then you must place on it the resistor 

which was removed from that zone. It is a rule that the 
distance  between  two  buttons  does  not  exceed  30m 
and all buttons should be placed at a height of about 
1.4m  from  the    floor.

 

The  diagram  below  shows  the 

connections between two buttons and a detector to a 
zone  of  a  fire  detection  panel.

 

It  also  shows  the 

connection  of  the  resistor  to  the  last  button  of    that   
zone.

 

921536010_23_002

BS-536/MAR

BS-536/MAR

OUT   IN

OUT   IN

-R

U

T

O

 

-

-L

N I

T

 +

U

R

O

 +

L

N

 

I

T

E

R

M

IN

A

L

R

E

S

IS

T

O

R

DETECTOR`S

BASE

TO THE ZONE

OF THE PANEL

EN 54-11, IEC 60092-504, IEC 60533

 BS-536/MAR

Page

 1

 from

 2

Thank you for your trust in our products  

Olympia Electronics -  European manufacturer

Отзывы: