M300(A) MONITOR MODULE, C304(A) CONTROL MODULE, AND

I300(A) FAULT ISOLATOR MODULE INSTALLATION INSTRUCTIONS

This information is included as a quick reference installation guide. Refer to the appropriate Fire-Lite control panel installation man-
ual for detailed system information. If the modules will be installed in an existing operational system, inform the operator and local
authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules.

STATUS LED

ROTARY DECADE
ADDRESS SWITCHES

MODE TABS

M300(A) MAGNET 
TEST POSITION

A78-2318-01

Figure 1. Montior and Control Module

Conrols and Indicators

F300-03-01

1

I56-570-05

Fire-Lite Alarms, Inc., 12 Clintonville Rd, Northfield , CT 06472-1652 (203) 484-7161

NOTICE: This manual should be left with the owner/user of this equipment.

GENERAL DESCRIPTION
M300(A) MONITOR MODULES
 provide a two-wire, or fault-tolerant, initiating
circuit for normally open contact fire alarm and supervisory devices, or either
normally open or normally closed security devices. The LED indicator can be
latched on or returned to the normal mode by code command from the panel.
Rotary decade switches are used to set the address of each module.

C304(A) CONTROL MODULES allow a compatible control panel to switch dis-
crete contacts by code command. The control module offers a status LED that
can be latched on or returned to the normal mode by code command from the
panel. Rotary decade switches are used to set the address of each module.

The control module offers two modes of switching operation. As shipped, the
module is configured for switching an external power source to notification ap-
pliances. The external power source can be a DC power supply or an audio amplifier (up to 70.7 Vrms). In this mode, the mod-
ule reports supervision status of the connected loads to the control panel. Load circuit status is reported as a normal, open, or
shorted circuit. Two pairs of output termination points are available for fault-tolerant wiring. The second mode of switching op-
eration allows the panel to control one Form-C (SPDT) set of contacts. 

Circuit connections to the contacts are not supervised

by the module. This mode is enabled by breaking two external tabs on the module.

I300(A) FAULT ISOLATOR MODULES enable part of the communications loop to continue operating when a short circuit oc-
curs on it. An LED indicator blinks in the normal condition and turns on during a short circuit condition. The module will auto-
matically restore the entire communications loop to the normal condition when the short circuit is removed. (The isolator mod-
ule does not have decade switches.)

COMPATIBILITY REQUIREMENTS
To insure proper operation, these modules must be connected to addressable, listed compatible Fire-Lite control panels only.

MOUNTING M300(A), C304(A), AND I300(A) DEVICES
M300(A), C304(A), and I300(A) modules mount directly to 4 inch square elec-
trical boxes as shown in Figure 2A. The box must have a min. depth of 2

/

8

".

WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and

regulations. When using control modules in nonpower limited applica-
tions, the CB500 Module Barrier must be used to meet UL require-
ments for the separation of power-limited and nonpower-limited termi-
nals and wiring. The barrier must be inserted in a 4"x4"x2

/

8

" junction

box, and the control module must be placed into the barrier and at-
tached to the junction box (Figure 2A). The power-limited wiring must
be placed into the isolated quadrant of the module barrier (Figure 2B).

1. Install module wiring in accordance with the job drawings and appropriate

wiring diagrams (Figures 3 - 10).

2. Set the address on the M300 and C304 per job drawings. Record this ad-

dress and loop on the front of the module, if desired.

3. Secure module to electrical box (supplied by installer), as shown in Figure 2A.

M300(A) MAGNET TEST
The M300(A) Monitor module can be tested with Fire-Lite's M02-04-01 Test
Magnet (see Figure 1). The magnet test checks the module electronics and
connections to the control panel. Interfaced initiating and indicating devices
must be tested independently.

A78-2610-00

Figure 2A. Module

Mounting with Barrier

ISOLATED

QUADRANT

A78-2611-00

Figure 2B.

Содержание C304(A

Страница 1: ... wiring The second mode of switching op eration allows the panel to control one Form C SPDT set of contacts Circuit connections to the contacts are not supervised by the module This mode is enabled by breaking two external tabs on the module I300 A FAULT ISOLATOR MODULES enable part of the communications loop to continue operating when a short circuit oc curs on it An LED indicator blinks in the n...

Страница 2: ...ONNECT MODULES TO LISTED COMPATIBLE 9 8 7 6 M300 A FIRE LITE CONTROL PANELS ONLY PREVIOUS DEVICE COMMUNICATION LINE ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED EOL RESISTOR IS INTERNAL AT TERMINALS 8 9 ANY NUMBER OF UL LISTED CONTACT CLOSURE DEVICES MAY BE USE DO NOT MIX FIRE ALARM INITIATING SUPERVISORY OR SECURITY DEVICE ON THE SAME MODULE INITIATING DEVICE CIRCUIT NFPA STYLE D POWER LIMITE...

Страница 3: ...70 7 Vrms MAX AMP WIRE SUPERVISION CIRCUIT SPEAKER SWITCHING CIRCUIT NFPA STYLE W SPEAKERS MUST BE LISTED FOR FIRE PROTECTION MAXIMUM LOAD 43 75 WATTS MAX UP TO 70 7 Vrms 35 POWER FACTOR WIRES MUST BE SUPERVISEDD PER NFPA WHEN A 70 7V AUDIO AMPLIFIER IS USED TERMINALS 1 AND 2 ARE POWER LIMITED WHILE TERMINALS 3 9 ARE NONPOWER LIMITED IN THIS CASE THE CB500 BARRIER IS REQUIRED OTHERWISE ALL TERMINA...

Страница 4: ...I300 A FAULT ISOLATOR MODULE I300 A SEE FIRE LITE PRODUCT MANUAL FOR WIRE SPECIFICATIONS INSTALLATION WARNINGS AND NOTES Control and isolator modules use a latching relay that can change states if it is subjected to mechanical shocks or jarring As a result although modules are shipped with their relays in the open state the contacts may have closed during shipment Con necting an auxiliary control ...

Отзывы: