F300-03-01
4
I56-570-05
© Fire-Lite Alarms, Inc. 1996
A78-2287-04
FIGURE 10. I300 FAULT ISOLATOR MODULE WIRING
1 (–)
2 (+)
MODULE
FROM PANEL OR
(+)
(–)
TO NEXT
(+)
(–)
DEVICE
(+)
(–)
CONTROL
CONNECT MODULES TO LISTED COMPATIBLE
9
8
7
6
5
3
4
RELAY COMMON
NORMALLY CLOSED
FORM "C" RELAY OPERATION WHEN
BOTH TABS J1 AND J2 ARE BROKEN.
J1 & J2
MODULE DOES NOT SUPERVISE CIRCUITS
CONTROLLED BY FORM C CONTACT.
NORMALLY OPEN
RELAY CONTACT RATINGS:
INDUCTIVE: 1 A @ 30 VDC (.6 PF)
RESISTIVE: 2 A @ 30 VDC
PILOT DUTY: .6 A @ 30 VDC (.35 PF)
.3 A @ 110 VDC (.35 PF)
.3 A @ 120 VAC (.35 PF)
C304(A)
CONTROL PANELS ONLY
PREVIOUS DEVICE
COMMUNICATION LINE
SEE FIRE-LITE PRODUCT
MANUAL FOR WIRE
SPECIFICATIONS
BREAK OFF TABS
J1 & J2 TO ENABLE
FORM C OPERATION
ALL WIRING SHOWN IS POWER LIMITED
(+)
(+)
(–)
1 (–)
2 (+)
1 (–)
2 (+)
(+)
(–)
(+)
(–)
1 (–)
2 (+)
1 (–)
2 (+)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
1 (–)
2 (+)
(+)
(–)
1 (–)
2 (+)
1 (–)
2 (+)
3 (–)
4 (+)
(–)
(+)
(+)
(–)
(–)
1 (–)
2 (+)
3 (–)
4 (+)
1 (–)
2 (+)
3 (–)
4 (+)
1 (–)
2 (+)
3 (–)
4 (+)
(+)
(–)
(+)
(–)
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED.
(+)
(–)
(+)
(–)
GROUPS OF ADDRESSABLE DEVICES ARE SEPARATED BY FAULT ISOLATOR
GROUP OF DEVICES IF A SHORT CIRCUIT OCCURS ON THE
SIGNALING LINE CIRCUIT WITHIN THAT GROUP.
A PAIR OF FAULT ISOLATOR MODULES WILL DISCONNECT A
FIRE-LITE UL LISTED COMPATIBLE
CONTROL PANEL
MODULES. ANY COMBINATION OF COMPATIBLE,
LISTED DEVICES MAY BE MIXED WITHIN A GROUP.
COMMUNICATION LINE
FAULT ISOLATOR
MODULE
I300(A)
FAULT ISOLATOR
MODULE
I300(A)
FAULT ISOLATOR
MODULE
I300(A)
FAULT ISOLATOR
MODULE
I300(A)
SEE FIRE-LITE PRODUCT
MANUAL FOR
WIRE SPECIFICATIONS
INSTALLATION WARNINGS AND NOTES
Control and isolator modules use a latching relay that can change states if it is subjected to mechanical shocks or jarring. As a
result, although modules are shipped with their relays in the open state, the contacts may have closed during shipment. Con-
necting an auxiliary control circuit to closed relay contacts in a control module can cause an unexpected, and possibly danger-
ous, activation of that circuit. Therefore, do NOT connect an auxiliary control circuit to the relay contacts before ensuring that
they are in their open (standby) state. Make sure that the contacts are open by allowing the control panel to poll the module at
least once, as indicated when the LED blinks.
If the contacts of several isolator modules are closed when system power is initially applied, it increases the load on upstream
modules, causing their relays to open. This prevents the proper application of power to the entire system. To correct this, con-
nect a temporary jumper between terminals 2 and 3 on all isolator modules whose LEDs are continuously lit OR interrupt the
signal line circuit after the last open isolator. The panel must delay communications for at least one minute after power is ap-
plied to allow all system devices to power up past the 7 volt threshold.
A78-2286-03
A78-1953-02
FIGURE 9. C304 CONTROL MODULE IN RELAY OUTPUT MODE