1 (–)
2 (+)

MODULE

FROM PANEL OR

(+)

(–)

TO NEXT

(+)

(–)

DEVICE

(+)

(–)

3 (–)
4 (+)

(+) 9
(–) 8

(–) 7

(+) 6

XXX 5

CONTROL

(–)

(+)

(–)

(+)

XXX - DO NOT

USE TERMINAL 5

TO NEXT CONTROL MODULE 
LAST MODULE MUST RETURN
WIRES FOR SUPERVISION

MODULE POLARITIES ARE

SHOWN IN ALARM

CONNECT MODULES TO LISTED COMPATIBLE

AUDIO BRANCH CIRCUIT

3 & 4. BREAK WIRE TO ENSURE

SUPERVISION OF CONNECTIONS.

DO NOT LOOP WIRE AROUND TERMINALS

ALL WIRING SHOWN IS SUPERVISED.

(+)

C304(A)

FIRE-LITE CONTROL PANELS ONLY

PREVIOUS DEVICE

EOL RESISTOR IS
INTERNAL ACROSS
TERMINALS 8 AND 9

SEE FIRE-LITE PRODUCT

MANUAL FOR

WIRE SPECIFICATIONS

COMMUNICATION LINE

(–)

AUDIO AMPLIFIER

70.7 Vrms MAX.

AMP. WIRE

SUPERVISION

CIRCUIT

SPEAKER SWITCHING CIRCUIT - NFPA STYLE X

SPEAKERS MUST BE LISTED FOR FIRE PROTECTION

MAXIMUM LOAD: 43.75 WATTS MAX.

UP TO 70.7 Vrms (.35 POWER FACTOR)

(+)

(–)

BYPASS CAPACITORS:  100 

µ

f, 10V

 

A2143-20  NONPOLARIZED
                  <10 

µ

A LEAKAGE

WIRES MUST BE SUPERVISEDD PER NFPA

WHEN A 70.7V AUDIO AMPLIFIER IS USED, TERMINALS 1 AND 2 ARE POWER LIMITED,
WHILE TERMINALS 3-9 ARE NONPOWER LIMITED. IN THIS CASE THE CB500 BARRIER 
IS REQUIRED. OTHERWISE, ALL TERMINAL WIRING IS POWER LIMITED.  THE CB500
INCLUDES A LABEL INDICATING WHICH TERMINALS ARE NONPOWER LIMITED. THIS
LABEL MUST BE PLACED OVER THE POWER-LIMITED TERMINAL INFORMATION ON 
THE NAMEPLATE LABEL, PRESENT ON THE MODULE HOUSING.  

1 (–)
2 (+)

MODULE

FROM PANEL OR

(+)

(–)

TO NEXT

(+)

(–)

DEVICE

(+)

(–)

3 (–)
4 (+)

(+) 9
(–) 8

(–) 7

(+) 6

XXX 5

CONTROL

(–)

(+)

(–)

(+)

XXX - DO NOT

USE TERMINAL 5

TO NEXT CONTROL MODULE 
LAST MODULE MUST RETURN
WIRES FOR SUPERVISION

MODULE POLARITIES ARE

SHOWN IN ALARM

CONNECT MODULES TO LISTED COMPATIBLE

AUDIO BRANCH CIRCUIT

3 & 4. BREAK WIRE TO ENSURE

SUPERVISION OF CONNECTIONS.

DO NOT LOOP WIRE AROUND TERMINALS

ALL WIRING SHOWN IS SUPERVISED.

(+)

C304(A)

FIRE-LITE CONTROL PANELS ONLY

PREVIOUS DEVICE

47 K EOL
RESISTOR
A2143-00

SEE FIRE-LITE PRODUCT

MANUAL FOR

WIRE SPECIFICATIONS

COMMUNICATION LINE

(–)

AUDIO AMPLIFIER

70.7 Vrms MAX.

AMP. WIRE

SUPERVISION

CIRCUIT

SPEAKER SWITCHING CIRCUIT - NFPA STYLE W

SPEAKERS MUST BE LISTED FOR FIRE PROTECTION

MAXIMUM LOAD: 43.75 WATTS MAX.

UP TO 70.7 Vrms
(.35 POWER FACTOR)

(+)

(–)

WIRES MUST BE SUPERVISEDD PER NFPA

WHEN A 70.7V AUDIO AMPLIFIER IS USED, TERMINALS 1 AND 2 ARE POWER LIMITED,
WHILE TERMINALS 3-9 ARE NONPOWER LIMITED. IN THIS CASE THE CB500 BARRIER 
IS REQUIRED. OTHERWISE, ALL TERMINAL WIRING IS POWER LIMITED.  THE CB500
INCLUDES A LABEL INDICATING WHICH TERMINALS ARE NONPOWER LIMITED. THIS
LABEL MUST BE PLACED OVER THE POWER-LIMITED TERMINAL INFORMATION ON 
THE NAMEPLATE LABEL, PRESENT ON THE MODULE HOUSING.  

A78-2284-04

FIGURE 7. TYPICAL C304 WIRING FOR SPEAKER SUPERVISION AND SWITCHING, NFPA STYLE W

F300-03-01

3

I56-570-05

*Canadian models have a resistive rating of 1.5A @ 30 VDC in this configuration.

A78-2283-05

FIGURE 6. TYPICAL C304 FAULT TOLERANT INDICATING CIRCUIT CONFIGURATION, NFPA STYLE X

A78-2285-04

FIGURE 8. TYPICAL C304 FAULT TOLERANT WIRING FOR SPEAKER SUPERVISION AND SWITCHING, NFPA STYLE X

1 (–)
2 (+)

MODULE

FROM PANEL OR

(+)

(–)

TO NEXT

(+)

(–)

DEVICE

(+)

(–)

3 (–)
4 (+)

(+) 9
(–) 8

(–) 7

(+) 6

XXX 5

CONTROL

(–)

(+)

(–)

(+)

UL LISTED EOL RELAY

SHOWN ENERGIZED

24 VDC COIL

A77-716B

XXX - DO NOT

USE TERMINAL 5

TO NEXT CONTROL MODULE OR END

OF LINE RELAY (EOLR); ONE EOLR

REQUIRED PER 24 VDC BRANCH CIRCUIT

MODULE POLARITIES ARE

SHOWN IN ALARM

CONNECT MODULES TO LISTED COMPATIBLE

USE UL LISTED INDICATING APPLIANCES

RESISTIVE: 2 A @ 30 VDC*

INDUCTIVE: 1 A @ 30 VDC (.6 PF)

PILOT DUTY: .6 A @ 30 VDC (.35 PF)

MAXIMUM LOAD:

BRANCH CIRCUIT

3 & 4. BREAK WIRE RUN TO PROVIDE

SUPERVISION OF CONNECTIONS.

DO NOT LOOP WIRE ON TERMINALS

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED

(+)

ISOLATED  REGULATED

POWER SUPPLY, LISTED FOR FIRE

PROTECTION WITH BATTERY BACKUP

(MONITOR LOSS OF PRIMARY POWER)

C304(A)

FIRE-LITE CONTROL PANELS ONLY

INDICATING APPLIANCE CIRCUIT (IAC) - NFPA STYLE X

PREVIOUS DEVICE

EXTERNAL POWER SOURCE MUST BE

POWER LIMITED PER NFPA 70

EOL RESISTOR IS
INTERNAL ACROSS
TERMINALS 8 AND 9

SEE FIRE-LITE PRODUCT

MANUAL FOR

WIRE SPECIFICATIONS

COMMUNICATION LINE

(–)

Содержание C304(A

Страница 1: ... wiring The second mode of switching op eration allows the panel to control one Form C SPDT set of contacts Circuit connections to the contacts are not supervised by the module This mode is enabled by breaking two external tabs on the module I300 A FAULT ISOLATOR MODULES enable part of the communications loop to continue operating when a short circuit oc curs on it An LED indicator blinks in the n...

Страница 2: ...ONNECT MODULES TO LISTED COMPATIBLE 9 8 7 6 M300 A FIRE LITE CONTROL PANELS ONLY PREVIOUS DEVICE COMMUNICATION LINE ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED EOL RESISTOR IS INTERNAL AT TERMINALS 8 9 ANY NUMBER OF UL LISTED CONTACT CLOSURE DEVICES MAY BE USE DO NOT MIX FIRE ALARM INITIATING SUPERVISORY OR SECURITY DEVICE ON THE SAME MODULE INITIATING DEVICE CIRCUIT NFPA STYLE D POWER LIMITE...

Страница 3: ...70 7 Vrms MAX AMP WIRE SUPERVISION CIRCUIT SPEAKER SWITCHING CIRCUIT NFPA STYLE W SPEAKERS MUST BE LISTED FOR FIRE PROTECTION MAXIMUM LOAD 43 75 WATTS MAX UP TO 70 7 Vrms 35 POWER FACTOR WIRES MUST BE SUPERVISEDD PER NFPA WHEN A 70 7V AUDIO AMPLIFIER IS USED TERMINALS 1 AND 2 ARE POWER LIMITED WHILE TERMINALS 3 9 ARE NONPOWER LIMITED IN THIS CASE THE CB500 BARRIER IS REQUIRED OTHERWISE ALL TERMINA...

Страница 4: ...I300 A FAULT ISOLATOR MODULE I300 A SEE FIRE LITE PRODUCT MANUAL FOR WIRE SPECIFICATIONS INSTALLATION WARNINGS AND NOTES Control and isolator modules use a latching relay that can change states if it is subjected to mechanical shocks or jarring As a result although modules are shipped with their relays in the open state the contacts may have closed during shipment Con necting an auxiliary control ...

Отзывы: