www.mircomgroup.com
LT-6155
Rev. 0 Oct 2021
MPS-800(U) Series
Fire Alarm Manual Station
1
Mircom’s MPS-800(U) Series Fire Alarm Manual Stations provide
manual fire alarm activation.
This guide covers these models:
MPS-810 Single Stage, Dual Action, Conventional Manual Station
MPS-810U Single Stage, Dual Action Conventional Manual
Station (US)
MPS-802 Two Stage, Dual Action, Conventional Manual Station
Specifications & Dimensions
Compatible with Mircom Fire Alarm Control Panels
Electrical Rating:
1 A at 30 VDC
Dimensions:
139 mm H x 104 mm W x 34 mm D
(5 1/2” H x 4 1/8” W x 1 3/8” D)
Install the manual station
Contents of kit
MPS-810(U): 2 mounting screws, 2 reset keys (black)
MPS-802: 2 mounting screws, 2 reset keys (black), 2 stage two
keys
A. Open
1.
Insert the reset key into the reset keyhole and turn it.
2.
Pull the cover open.
Figure 1 Front of manual station
Figure 2 Opening the station
Notes
• Environment: Outdoor, wet
• Do not change factory applied finishes.
• Wire as shown so that supervision of connections is
maintained.
• Maximum wire size: 14 AWG
• ADA compliant.
• To be installed per ADA 4.27.1 to 4.27.4 inclusive.
• Wiring must be in accordance with CSA C22.1, Canadian
Electrical Code, Part I, Safety Standard for Electrical
Installations, Section 32 and CAN/ULC-S524, Standard for
Installation of Fire Alarm Systems.
• All manual fire alarm stations shall be installed as per the
specific requirements outlined in the UL/ULC codes, as well
as all other applicable national or local codes. Final
acceptance is subject to the local authority having
jurisdiction.
RESET
KEYHOLE
STAGE TWO
KEYHOLE
(MPS-802 ONLY)
PUSH BAR
PULL
HANDLE
COVER
MOUNTING
PLATE