LT-6155

 Rev. 0 Oct 2021

MPS-800(U) Series

Fire Alarm Manual Station

1

Mircom’s MPS-800(U) Series Fire Alarm Manual Stations provide 
manual fire alarm activation.

This guide covers these models:

MPS-810 Single Stage, Dual Action, Conventional Manual Station
MPS-810U Single Stage, Dual Action Conventional Manual 
Station (US)
MPS-802 Two Stage, Dual Action, Conventional Manual Station

Specifications & Dimensions

Compatible with Mircom Fire Alarm Control Panels

Electrical Rating:

1 A at 30 VDC

Dimensions:

139 mm H x 104 mm W x 34 mm D
(5 1/2” H x 4 1/8” W x 1 3/8” D)

Install the manual station

Contents of kit

MPS-810(U): 2 mounting screws, 2 reset keys (black)
MPS-802: 2 mounting screws, 2 reset keys (black), 2 stage two 
keys

A. Open

1.

Insert the reset key into the reset keyhole and turn it.

2.

Pull the cover open.

Figure 1 Front of manual station

Figure 2 Opening the station

Notes

• Environment: Outdoor, wet
• Do not change factory applied finishes.
• Wire as shown so that supervision of connections is 

maintained.

• Maximum wire size: 14 AWG
• ADA compliant.
• To be installed per ADA 4.27.1 to 4.27.4 inclusive.
• Wiring must be in accordance with CSA C22.1, Canadian 

Electrical Code, Part I, Safety Standard for Electrical 
Installations, Section 32 and CAN/ULC-S524, Standard for 
Installation of Fire Alarm Systems.

• All manual fire alarm stations shall be installed as per the 

specific requirements outlined in the UL/ULC codes, as well 
as all other applicable national or local codes. Final 
acceptance is subject to the local authority having 
jurisdiction.

RESET 

KEYHOLE
STAGE TWO 

KEYHOLE 

(MPS-802 ONLY)

PUSH BAR
PULL 

HANDLE

COVER

MOUNTING 

PLATE