Astra-45A
Addressable hardwired
fire manual call point
User guide
Manufacturer:
ZAO NTC TEKO
420108, Russia, Kazan,
Gafuri str., 71
Tel.:+7(843) 528-03-69
[email protected]
www.teko.biz
Made in Russia
Rev. 45
А-v2_0_instr_en
1 FUNCTION
The addressable hardwired fire manual call point
(further “Call Point” or “Astra-45A”, “device”) is de-
signed to manually trigger a fire alarm by pressing the
drive element (button), to generate a
“Fire” notification
and to
transmit the “Fire” notification via Signaling
Line Circuit (SLC) through Astra-A RPA to Control
Panels: Astra
– 812 Pro or Astra – 8945 Pro (version
5_5 or version higher).
Astra-45A provides isolation of the SLC section in
which a short circuit has occurred (Control Panel
version 5_5 and version higher).
Astra
– 45A is powered by Astra-A RPA.
2
SPECIFICATION
Power supply voltage, V ................................ 7,5 - 27,6
Dimensions, mm
.…………………………… 110×94×48
Operating Conditions
Temperature range,
°
С
....................... from - 30 to + 55
Relative air humidity
, % ...................... up to 93 at +40
°
С
without moisture condensation
3 DELIVERY SET
Delivery set includes: unlock key (large)
– 1 pc, push
key (small)
– 1 pc, labels – 2 pcs,
fastening parts (dow-
els
– 2 pcs, screws – 2 pcs),
user guide
– 1 pc
.
4 INDICATION
Status
LED
Standby mode
x1 green flash with a period of 8-9
sec.
Fire alarm
x1 red flash with a period of 2 sec.
Fire test
x1 red flashes with a period of 2
sec. during 20 sec.
Power failure
x3 red flashes with a period of 25
sec. at a supply voltage below 8 V
Power failure
SLC1 or SLC2
x1 yellow flashes with a period of 3
sec. at a short circuit or voltage
below 8 V on the supply line L1 or
L2
Data lines
SLC1 or SLC2
failure
x2 yellow flashes with a period of 3
sec. at Data lines SLC1 or SLC2
short circuit
Circuit break
Any possible variant from the table
Command
receiving from
Laser pointer
(LP)
x1 red switching on for 2-5 sec
5 ADDING TO THE SYSTEM
1)
Connect the RPA to the Control Panel using RS-
485 interface.
2) Add the Astra-RPA to the Control Panel according to
the user guide of the Control Panel Astra-812 Pro or the
PKM Astra Pro or Pconf-Pro PC built-in. Install the device
at the selected location (see point 8, actions 1)-5)).
Note:
It is recommended to install all Call Points
before
registration, because their registration is carried out
using the Astra-942 (L P) and supplied separately.
3) Run the Control Panel mode of Device Adding in the
RPA through Astra Pro PKM or the Control Panel
“Astra-812 Pro” menu in accordance with the Control
Panel manual.
It takes 60 sec to register a device.
4) Run the registration Astra
– 45A mode:
- press the lower button on the LP
and hold it until the beam appears