- irradiate the Astra
– 45A indicator at least
1 sec. (the indicator should turn on red for 2 sec.)
WARNNING!
Running registration for several devices at one and
the same time is forbidden.
5) Registration running check:
In case of successful registration, you will see
“Detector” or “Detector is added” on the screen.
In case of unsuccessful registration repeat ac-
tions from 4) to 6
6 REMOVING FROM THE SYSTEM
Removing any device form RPA
’s memory can be
performed using installation program modules PKM
Astra Pro or Astra
– 812 Pro menu.
7 INSTALLATION PLACE
It is recommended to install the device in an accessi-
ble place along escape routes, in corridors, on stair-
cases, at exits.
8 INSTALLATION PROCEDURE
1) Open the device with a key with a beard
2) Mount the base
3) Connect the SLC power cables (terminals "+")
and "-") and the SLC data cables (terminals "A" and "B")
coming from the RPA through the holes for cable enter-
ing in the device base. Recommended cable type
–
FRLS 2×2×0.5
The group of terminal blocks L1 or L2 for connecting the
incoming or outgoing ALS can be selected randomly.
ATTENTION!
Connect cables with de-energized lines only!
4) Assemble the device:
- press the device cover against
the base to align the grooves
- slide the cover down until the
latch locks
5) Register the device in the RPA (see section 5)
6) Perform the device testing (see section 9)
9 TEST
1) Press the button. A white (or yellow) curtain will ap-
pear at the top of the cover, indicating that the device is
in alarm. The red indicator of the device will blink with
short flashes with a period of 2 sec.
2) Check the "Fire" notification on the screen or
indicator of the Control Panel and/or in the PKM Astra
Pro or in Pconf Pro program.
3) Return the device to Standby mode:
- insert the push key into the hole on the lower end of
the device until it stops (until the button is unlocked);
- remove the key
- disable fire alarm with a registered identifier
- check the device and the Control Panel returning to
Standby mode
4) Activate the "Test" mode:
5) press the red button on Laser Pointer
- direct the laser beam at the indicator
- irradiate the indicator for 1 sec. The device indi-
cator should turn on red for 5 sec. Check the "Fire
Test" notification in the device indicator. In the
event log of PKM Astra Pro or Control Panel As-
tra-
812 Pro, an entry “Fire Test” will be made, and
the message “Fire Test” will be displayed in the
Pconf-Pro.
10 WARRANTY
The operation warranty period is 5 years from the date
of operation start-up, but no longer than 5 years 6
months from the date of manufacturing, in condition of
compliance with the requirements of the current tech-
nical manuals and user guide.