background image

 

- irradiate the Astra 

– 45A indicator at least 

1 sec. (the indicator should turn on red for 2 sec.) 

 

WARNNING!  
Running registration for several  devices at one and 
the same time is forbidden.

 

5)  Registration running check: 

  In  case  of  successful  registration,  you  will  see 

“Detector” or “Detector is added” on the screen.  

  In  case  of  unsuccessful  registration  repeat  ac-

tions from 4) to 6

 

 

6 REMOVING FROM THE SYSTEM 
 

Removing  any  device  form  RPA

’s  memory  can  be 

performed  using  installation  program  modules  PKM 
Astra Pro or Astra 

– 812 Pro menu.  

7 INSTALLATION PLACE 

It  is  recommended  to  install  the  device  in  an  accessi-
ble  place  along  escape  routes,  in  corridors,  on  stair-
cases, at exits. 

 

8 INSTALLATION  PROCEDURE  

1) Open the device with a key with a beard 

 

 

 

2)  Mount the base  
3)  Connect the SLC power cables (terminals "+") 

 

and "-") and the SLC data cables (terminals "A" and "B") 
coming from the RPA through the holes for cable enter-
ing  in  the  device  base.  Recommended  cable  type 

– 

FRLS 2×2×0.5 

 

The group of terminal blocks L1 or L2 for connecting the  
incoming or outgoing ALS can be selected randomly. 

 
ATTENTION!

  

Connect cables with de-energized lines only!

  

 

4) Assemble the device: 

-  press the device cover against 

the base to align the grooves 

-  slide  the  cover  down  until  the 

latch locks 

 
 
 

 

5) Register the device in the RPA (see section 5) 
6) Perform the device testing (see section 9) 

 
9 TEST 
 

1) Press  the  button.  A  white  (or  yellow)  curtain  will  ap-
pear at the top of the cover, indicating that the device is 
in  alarm.  The  red  indicator  of  the  device  will  blink  with 
short flashes with a period of 2 sec. 
2)  Check  the  "Fire"  notification  on  the  screen  or 
indicator of the Control Panel and/or in the PKM Astra 
Pro or in Pconf Pro program. 
3)  Return the device to Standby mode: 
- insert the push key into the hole on the lower end of 
the device until it stops (until the button is unlocked); 

- remove the key  
- disable fire alarm with a registered identifier 
-  check  the  device  and  the  Control  Panel  returning  to 
Standby mode 
4)  Activate the "Test" mode: 
 

 

 
5)  press the red button on Laser Pointer 

-  direct the laser beam at the indicator 
-  irradiate the indicator for 1 sec. The device indi-
cator should turn on red for 5 sec. Check the "Fire 
Test"  notification  in  the  device  indicator.  In  the 
event  log  of  PKM  Astra  Pro  or  Control  Panel  As-
tra-

812 Pro, an entry “Fire Test” will be made, and 

the  message  “Fire  Test”  will  be  displayed  in  the 
Pconf-Pro. 

 
10  WARRANTY 

The operation warranty period is 5 years from the date 
of  operation  start-up,  but  no  longer  than  5  years  6 
months from the date of manufacturing, in condition of 
compliance  with  the  requirements  of  the  current  tech-
nical manuals and user guide.

 