MPS-800(U) Series
Fire Alarm Manual Station
www.mircomgroup.com
LT-6155
Rev. 0 Oct 2021
2
B. Wire
Note:
The maximum wire size is 14 AWG.
1.
Strip wires to 10 mm (25/64”) maximum.
2.
Push the wire into the terminal.
Note:
The terminals have a push-in lock. To remove the wire,
push the terminal in with the screwdriver and pull out the
wire at the same time. see Figure 3.
Figure 3 Removing the wire
3.
Wire as shown in Figure 4.
Figure 4 Wiring
C. Mount
Flush mount indoor: Single-gang electrical box.
Flush mount outdoor: Single-gang electrical box with STI-1250
(Shallow Cover with Gasket)
Surface mount indoor: BB-800 backbox with or without STI-1230
(Deep Cover without Gasket)
Surface mount outdoor: BB-800 backbox with STI-3150 (Deep
Cover with Gasket)
Note:
Mount the manual station with the Mircom logo on the
bottom.
Figure 5 Back of manual station
Using the manual station
Activate the alarm
1.
Push in the push bar.
2.
Pull down the pull handle.
A qualified person must reset the station by opening it with the
reset key. See
Resetting the manual station
below.
Activate the stage two alarm (MPS-802)
•
Insert the stage two key into the stage two keyhole, and then
turn the key.
The stage two alarm activates immediately.
Note:
The stage two alarm will activate automatically a certain
amount of time after the handle has been pulled if no
action is taken. This time is set in the Fire Alarm Control
Panel.
Reset the manual station
Note:
Resetting the station does not cancel the alarm at the
panel.
1.
Insert the reset key into the reset keyhole and turn it.
2.
Pull the cover open. The switch is now reset.
3.
Close and lock the station with the reset key.
4.
Reset the Fire Alarm Control Panel to reset the alarm.
TO REMOVE WIRE, PLACE
A SMALL FLATHEAD
SCREWDRIVER INTO THE
GROOVE AND PUSH IN.
AT THE SAME TIME, PULL
THE WIRE OUT OF THE
TERMINAL.
TO NEXT STATION OR
LEAVE IT EMPTY
FROM
PREVIOUS
STATION
TO NEXT KEYSWITCH
OR END OF LINE DEVICE
(MPS-802 ONLY)
í
+
+
FROM
PREVIOUS
KEYSWITCH
(MPS-802 ONLY)
+
+
í
í
í
MOUNTING
HOLES