background image

DF-51276  —  Page 1 of 4

GENERAL

The 

MS-9200

 is a compact, cost-effective, addressable

fire alarm control panel with a capacity of 198 

Fire•Lite

300 Series

 devices.  A single Signaling Line Circuit (SLC)

loop supports up to 99 smoke detectors and 99 control or

monitor modules. The panel uses surface-mount technol-

ogy and is designed for ease of installation and program-

ming.  It features the latest in fire protection technology,

including maintenance alert and automatic detector test.

FEATURES

• SLC supports up to 198 addressable devices (99 detec-

tors and 99 monitor or control modules).

• SLC can be configured for Style 4, 6, or 7 operation.
• Dual Integral Notification Appliance (bell, signal) Circuits

(NAC's), Style Y or Z (Class B or A).

• 3.0 Amp Notification Appliance (bell, signal) power, ex-

pandable to 6.0 Amperes.

• NAC's may be programmed for Steady, March Time,

Temporal or California Code 

(requires software P/N 73750

or greater).

• Alarm, trouble and supervisory relays, standard.
• Maintenance alert warns when smoke detector dust ac-

cumulation is excessive.

• Optional UDACT-F Digital Alarm Communicator reports

56 zones or 198 points to a Central Station.

• Optional LCD-40 Series alphanumeric, 40-character,

backlit remote serial annunciators operate over high-

speed EIA-485 port.  Up to 32 may be supported by MS-

9200 

(requires software P/N 73750 or greater).

• Optional printer interface — UL listed for permanent

attachment.

• Integral 40-character LCD display with backlighting.
• Keypad programmable on panel, with two user-defined

passwords, plus an Autoprogram feature.

• Custom English labels per point may be manually en-

tered or selected from an internal library file.

• Autoprogram and Walk Test features identify 2 or more

devices set to same address.

• Real-time clock/calendar.
• History file with 500-event capacity.
• Waterflow or supervisory selection per monitor point.
• System alarm verification, smoke only.
• Presignal delay option per NFPA 72.
• Silence Inhibit and Auto Silence timer options.
• Battery charger for up to 60 hours of standby power.
• Fuseless, power-limited technology meets new UL power-

limiting requirements, effective May 1, 1995.

• Rapid poll algorithm for manual stations.  Responds to

alarm/activation in less than two seconds.

• Operates with untwisted, unshielded wire (up to 1,000

feet) for retrofit applications (U.S. Patent 5,210,523).

• 300 Series addressable devices feature decimal address

selection.  Address of each device can be easily set in the

field by use of a screwdriver.  Smoke detectors also

feature a plug-in wiring connector for ease of installation

and serviceability.

• Remote Acknowledge/Silence/Reset/Drill via M300 mod-

ules.

• SLC loop maximum length 10,000 ft. @ 12 AWG (3.25

mm

2

).

S624

(MS-9200, MS-9200E)

CS68

(MS-9200C)

0X9A3.AY

 (MS-9200, CP300,

SD300, BG-10LX,

M300, M301, M302,

C304, I300)

(Requires DP-9200)

0Y6A3.AY

 (SD300T)

MEA

16-94-E

(MS-9200 & M302)

3-94-E

(M300, M301,

I300,

SD300, CP300)

326-94-E

(SD300T, C304)

7165-0075:158

(MS-9200)

7300-0075:159

(M300, M301, I300, C304)

7300-0075:162

(M302)

7272-0075:172

(SD300, SD300T)

MS-9200

SYSTEM ALL NORMAL

10:12  A  MON  01/15/96

MS-9200(C/E)

Addressable

Fire Alarm Control Panel

A1-100

March 23, 1998

Section:  Addressable

ISO-9001

Engineering and Manufacturing

Quality System Certified to

International Standard ISO-9001

Made in the U.S.A.

This document is not intended to be used for installation purposes.  We try to keep our

product information up-to-date and accurate.  We cannot cover all specific applications or

anticipate all requirements.  All specifications are subject to change without notice.  For

more information, contact 

Fire•Lite.  

 Phone: (203) 484-7161  FAX: (203) 484-7118

12 Clintonville Road, Northford, Connecticut   06472

Содержание MS-9200(C/E)

Страница 1: ...ame address Real time clock calendar History file with 500 event capacity Waterflow or supervisory selection per monitor point System alarm verification smoke only Presignal delay option per NFPA 72 Silence Inhibit and Auto Silence timer options Battery charger for up to 60 hours of standby power Fuseless power limitedtechnologymeetsnewULpower limiting requirements effective May 1 1995 Rapid poll ...

Страница 2: ...ciator LDM 32F Graphic Annunciator up to 56 zones or 198 points AFM Series Annunciators UDACT F D A C T can be installed within MS 9200 or remotely in ABS 8RF or UBS 1F remote backbox Miniature version of M300 Optional Reverse Polarity City Box Output order RTM 8F Notification Appliance bell signal Circuits NAC s Optional EIA 232 interface module for PC computer or diagnostic printer PIM 24 requir...

Страница 3: ...TE For more detailed information on Compatible Annunciators for use with the MS 9200 please see the following data sheets document numbers LCD 40 DF 51474 AFM AFM X DF 51465 and LDM Series DF 51384 FIELD PROGRAMMING FEATURES Off Line Programming Create entire program in your office using a Windows based PC computer order pro gramming kit PK 9200W separately Upload Download system programming local...

Страница 4: ...ace with up to 32 LCD 40 annunciators AFM AFM X Series LED type fire annunciators ca pable of providing up to 56 software zones of annuncia tion Available in increments of 16 or 32 with expandable AFM X Series and non expandable AFM Series con figurations to meet a variety of applications LDM Series Lamp Driver Module series for use with custom graphic annunciators NOTE For more detailed informati...

Отзывы: