5-85
5-16 User Parameters
5
Ope
rati
ng Func
tions
• Use these parameters to set the limit value for the output torque (Pn5E: No. 1 Torque Limit, Pn5F:
No. 2 Torque Limit) of the Servomotor.
• Refer to information on the Torque Limit Selection (Pn03) to select the torque limits.
• The maximum torque in the forward and reverse directions is limited in Torque Control Mode, and
the settings of the Torque Limit Selection (Pn03) and No. 2 Torque Limit (Pn5F) are ignored.
• Make the settings as a percentage of the rated torque.
Example: Maximum torque is limited to 150%
• Refer to
on page 5-26 for information on torque limits and the torque limit
selection.
Pn5E
No. 1 Torque Limit
Setting range
0 to 500
Unit
%
Default setting
300
Power OFF
→
ON
---
Pn5F
No. 2 Torque Limit
Setting range
0 to 500
Unit
%
Default setting
100
Power OFF
→
ON
---
All modes
Position Speed
200
100
200
300
Torque (%)
300 (max.)
Forward
(Rated) (Maximum)
Speed
Reverse
Pn5E, Pn5F = 150
100 (rated)