• Use this parameter to select the FIR filter time constant used for the command pulses (FIR: Finite
impulse response).
• The higher the setting, the smoother the command pulses.
• If the setting is 0, the control cycle will be (0 + 1)
×
166 = 166
μ
s.
If the setting is 1, the control cycle will be (1 + 1)
×
166 = 332
μ
s.
Likewise, if the setting is 31, the control cycle will be (31 + 1)
×
166 = 5,312
μ
s.
Explanation of Settings
• If Pn4E is set to 0, the minimum time width of the ECRST signal will be as follows:
Pn4D
Smoothing Filter Setting
Setting range
0 to 31
Unit
---
Default setting
0
Power OFF
→
ON
Yes
Pn4E
Deviation Counter Reset Condition Setting
Setting range
0 to 2
Unit
---
Default setting
1
Power OFF
→
ON
---
Setting
Explanation
0
Clears the deviation counter when the signal is closed for 100
μ
s or longer.
1
Clears the deviation counter on the falling edge of the signal (open and then closed for
100
μ
s or longer).
2
Disabled
Position
Command
Input position command
Position command after
smoothing filter processing
Position command after FIR filter processing
tf = (Pn4E + 1)
×
Control cycle
Time
t
f
t
f
t
f
t
f
Response with position loop gain
Response with position
loop gain
Position
ECRST (pin 30)
100
μ
s min.
Содержание R88D-GT series
Страница 20: ...18 Table of Contents ...
Страница 234: ...3 133 3 8 Reactor Specifications 3 Specifications ...
Страница 448: ...7 37 7 5 Manual Tuning 7 Adjustment Functions ...
Страница 474: ...8 25 8 5 Periodic Maintenance 8 Troubleshooting ...
Страница 475: ...Chapter 9 Appendix 9 1 Connection Examples 9 1 9 2 Parameter Tables 9 11 ...
Страница 509: ......