10-22
10-5 Damping Control
OMNUC G5-Series AC Servo Drives Users Manual (Built-in MECHATROLINK-II communications type)
10
Adj
u
st
me
nt
Func
tions
Parameters Requiring Settings
Precautions for Correct Use
Stop operation before changing the parameters or switching with DFSEL.
It may not function properly or the effect may not be apparent under the following conditions.
Parameter
number
Parameter name
Description
Reference
Pn001
CONTROL mode
Selection
Set to the POSITION or FULL CLOSING CONTROL mode.
0 to 5: Switch control
6: Full closing control
Pn213
Damping Filter
Selection
Select the DAMPING FILTER SWITCHING mode
according to the condition of the unit.
0: Damping filter 1 or 2 enabled
3: Switching with command direction
Pn214
Damping
Frequency 1
Set damping frequency 1 to suppress vibration at the end of
the load in damping control.
If the damping control function is not used, set 0.
Pn215
Damping Filter 1
Setting
When the Damping Frequency 1 (Pn214) is set, reduce the
setting if torque saturation occurs or increase the setting to
increase operation speed. Normally 0 is set.
If the damping filter 1 is disabled, this parameter is also
disabled.
Pn216
Damping
Frequency 2
The function is the same with Pn214.
Pn217
Damping Filter 2
Setting
The function is the same with Pn215.
Pn218
Damping
Frequency 3
The function is the same with Pn214.
Pn219
Damping Filter 3
Setting
The function is the same with Pn215.
Pn220
Damping
Frequency 4
The function is the same with Pn214.
Pn221
Damping Filter 4
Setting
The function is the same with Pn215.
Item
Conditions under which the effect of damping control is inhibited
CONTROL
mode
• SPEED or TORQUE CONTROL mode
Load condition
• If forces other than position commands, such as external forces, cause vibration.
• If the damping frequency is outside the range of 1.0 to 200 Hz.
• If the ratio of the resonance frequency to anti-resonance frequency is large.
Содержание OMNUC G5 R88D-KN series
Страница 22: ......
Страница 164: ......
Страница 228: ......
Страница 274: ......
Страница 342: ......
Страница 392: ......
Страница 432: ......
Страница 450: ......
Страница 451: ...I OMNUC G5 Series AC Servo Drives Users Manual Built in MECHATROLINK II communications type Index ...
Страница 456: ......
Страница 457: ......