4 System Design
4 - 18
OMNUC G5-series (Pulse-train Input Type) AC Servomotors and Servo Drives User’s Manual
The following table shows the allowable current when there are 3 power supply wires. Use a current
below these specified values.
600-V Heat-resistant Vinyl Wire (HIV)
Wire Sizes and Allowable Current (Reference)
AWG size
Nominal cross-
sectional area
[mm
2
]
Configuration
[wires/mm
2
]
Conductive
resistance
[
Ω
/km]
Allowable current [A] for
ambient temperature
30°C
40°C
50°C
20
0.5
19/0.18
39.5
6.6 5.6 4.5
–
0.75
30/0.18
26.0 8.8 7.0 5.5
18
0.9
37/0.18
24.4
9.0 7.7 6.0
16
1.25
50/0.18
15.6
12.0 11.0 8.5
14
2.0 7/0.6
9.53
23
20
16
12
3.5
7/0.8
5.41
33
29
24
10
5.5
7/1.0
3.47
43
38
31
8
8.0
7/1.2
2.41
55
49
40
6
14.0
7/1.6
1.35
79
70
57
4
22.0
7/2.0
0.85
99
88
70
Содержание G5 R88D-KE Series
Страница 3: ...2 Page 2 53 For 1 000 r min Servomotors 900 W to 3 kW Current Contents Corrected Contents...
Страница 22: ...Manual Structure 18 OMNUC G5 series Pulse train Input Type AC Servomotors and Servo Drives User s Manual...
Страница 334: ...6 Applied Functions 6 52 OMNUC G5 series Pulse train Input Type AC Servomotors and Servo Drives User s Manual...
Страница 396: ...7 Parameter Details 7 62 OMNUC G5 series Pulse train Input Type AC Servomotors and Servo Drives User s Manual...
Страница 426: ...8 Operation 8 30 OMNUC G5 series Pulse train Input Type AC Servomotors and Servo Drives User s Manual...
Страница 498: ...Appendices A 32 OMNUC G5 series Pulse train Input Type AC Servomotors and Servo Drives User s Manual...
Страница 499: ...Index 1 I OMNUC G5 series Pulse train Input Type AC Servomotors and Servo Drives User s Manual Index...
Страница 504: ......
Страница 505: ......