Trouble locating and clearing procedures (continued) 1-93
DMS-100 Family NA100 Trouble Locating and Clearing Procedures Volume 2 of 2 LET0015 and up
Replacing a 3.5 in. disk drive unit
NTFX32BA
(end)
and press Enter.
where
ioc_no
is the number of the input/output controller (IOC)
port_no
is the number of the DDU port
33
To return the DDU to service, type
>RTS
and press Enter.
Example of a MAP display:
34
Pack the replaced DDU in a carton and send it to the correct repair location.
Note: For additional information on the return of equipment, refer to the
correct procedure in this document.
35
Record the following information in your office records:
•
the date of replacement of the damaged DDU
•
the serial number of the damaged DDU
•
the indications that prompted the DDU replacement
36
A major or minor alarm can rise under the IOD header of the MAP display at
the start of this procedure. Determine if the alarm cleared.
37
You cannot busy the IOM controller card when files are open. If you busy the
card, loss of billing data can result. For additional help, contact the person
responsible for the next level of support.
38
For additional help, contact the person responsible for the next level of
support.
39
The procedure is complete.
If the RTS command
Do
passed
step 34
failed
step 38
If the alarm
Do
cleared
step 39
did not clear
step 38
Port 16 Unit
0
(SCSI)
User
system
Drive_State
Status
BSY
Online