125
-
'11 • SCM-SM-110
Stays OFF
Keeps flashing
Error code
Remote controller:
LED
Green
Red
Indoor
Content
E42
Current cut (2/2)
Outdoor
–
1
time flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
After
resetting power for
several times does it
become normal?
NO
YES
Temporary noise may cause of anomaly.
If noise source can be found, take countermeasure.
Is the
checked result of power
transistor module
OK?
NO
• Is the space for installation of indoor and/or outdoor unit enough?
• Is there any short circuit of air on indoor and/or outdoor unit?
• At cooling, does the outdoor fan motor run?
Are the service valves fully opened?
Is the filter clogged?
• At heating, does the indoor fan motor run?
Are the service valves fully opened?
Is the filter clogged?
• Is there any liquid flooding?
Is the superheat within normal range?
Is the suction pipe temperature thermistor normal?
• Is there any anoumalous sound on the compressor?
YES
From previous page
YES
• Defective outdoor main
PCB
➞
Replace.
• Defective outdoor main
PCB
➞
Replace.
2. Error detection method
In order to prevent from
overcurrent of inverter,
if the current exceeds the
specifications, it makes the
compressor stopping.
3. Condition of Error displayed
•
If the output current of inveter
exceeds the specifications,
it makes the compressor
stopping.
4. Presumable cause
• Defective outdoor main PCB
• Faulty power supply
• Insufficient refrigerant amount
• Faulty compressor
• Faulty power transistor
module
Note:
Содержание SCM100ZJ-S1
Страница 64: ...63 11 SCM SM 110 Service data record form 55...
Страница 194: ...193 11 SCM SM 110 4 Ceiling cassette 4way compact type FDTC refer to page 157 to 172...
Страница 198: ...197 11 SCM SM 110 PJAO12D786...
Страница 223: ...222 11 SCM SM 110 4 way valve coil 1 Disconnect the connector 2 Loosen a screw and remove the coil Connector Screw Coil...
Страница 237: ...236 11 SCM SM 110 EEVB EEVC EEVA EEVD MARKING GREEN BLUE RED WHITE EEV A EEV D 46 WH 46 46 46 M YE OR BL RD Input 12VDC...