'11 • SCM-SM-110
(9) Crankcase heater
(a) Operating conditions
(When all the conditions below are satisfied)
①
After the operation mode is changed to stop and the compressor command speed becomes 0 rps continuously for 0 minutes.
②
When the temperature detected by the outdoor air temperature (Tho-A) is 0°C or lower after the compressor stops.
(8) Freezing cycle system protective control
(a) Starting condition:
This control starts when the following conditions are met.
)
When it has elapsed 0 minutes after the compressor was changed from OFF to ON in the cooling operation mode for
more than minutes.
)
When the compressor command speed has met the following conditions.
)
When the indoor air temperature of running indoor unit (Th) and the indoor heat exchanger temperature (Th) have
met the following condition even on one unit.
Note () Values in ( ) are for the model SCM0, , 0.
(b) Contents of control
)
Stop the compressor and delay the start, and then restarts.
)
Compressor stops by the abnormal stop when the compressor stop has occurred times in one hour.
Unit
Compressor
command speed
Indoor air temperature
(Th1,
℃
)
Indoor air temperature (Th1) and indoor
heat exchanger temperature (Th2)
Duration
1
0 (0) rps
0 <=
Th <= 0
Th - < Th
minute
2
0 (0) rps
3
0 (0) rps
Th - < Th
4
0 rps
Th - < Th
5
0 rps
6
0 rps
(b) Detail of operation
The crankcase heater operates, warming up the compressor, then refrigerant begins circulating smoothly when the cooler
starts its heating operation, and heating begins.
(c) Restoration conditions
When the temperature detected by the outdoor air temperature (Tho-A) reaches °C or higher, or the operation mode
changes from stop to cooling or heating.
(10) Inching prevention
When the compressor becomes to the thermo operation within minutes since operation start or becomes dehumidifying opera-
tion, the operation is continued with the compressor command speed of minimum rps forcibly.
(11) Compressor overheat protection
(a) Purpose:
(b) Detail of operation
1)
Discharge pipe temperature (˚C)
(Example) Fuzzy
95
105
115
3 minutes
3 minutes
3 minutes
105
̅
115
95
̅
105
95
̅
105
3 minutes
3 minutes
Tho-D
Содержание SCM100ZJ-S1
Страница 64: ...63 11 SCM SM 110 Service data record form 55...
Страница 194: ...193 11 SCM SM 110 4 Ceiling cassette 4way compact type FDTC refer to page 157 to 172...
Страница 198: ...197 11 SCM SM 110 PJAO12D786...
Страница 223: ...222 11 SCM SM 110 4 way valve coil 1 Disconnect the connector 2 Loosen a screw and remove the coil Connector Screw Coil...
Страница 237: ...236 11 SCM SM 110 EEVB EEVC EEVA EEVD MARKING GREEN BLUE RED WHITE EEV A EEV D 46 WH 46 46 46 M YE OR BL RD Input 12VDC...