219
-
'11 • SCM-SM-110
Sub PCB (Lower layer)
1.After removing the Main PCB,
disconnect all connectors on
Sub PCB.
①
Disconnect the connector
of CNEEV1.
(
for EEV1 & EEV2)
②
Disconnect the connector
of CNEEV2.
(
for EEV3 & EEV4)
③
Disconnect the connector
of CNTH.
(
for suction pipe temp.)
④
Disconnect the connector
of CNMAIN.
(Going to Main PCB)
⑤
Disconnect the connector
of CNHEAT.
(for crankcase heater)
⑥
Disconnect the connector
of CN20S.
(for 4-way valve)
⑦
Disconnect the connector
of CN20V.
(Going to Main PCB)
⑧
Disconnect the connectors
of CNA, CNB, CNC and
CND.
2.Loosen screws and disconnect
the grounding cables.
3.Disconnect the fasten
connector of the black cable.
Note : Be sure to do above
work after elapsing
3 minutes from power OFF.
4.Loosen a screw and pull up
the right side of the upper TB
to unlatch from the left side
square hole.
5. Loosen the screw of
N-terminal and disconnect
the white cable.
C N A
⑧
CNEEV2
②
CNEEV1
①
CNMAIN
④
CNHEAT(WH)
⑤
CN20S(RD)
⑥
CNTH
③
Grounding cable (G-1)
Grounding cable (G-2)
Grounding cable (G-1)
Grounding cable (G-2)
Grounding cable (G-3)
Grounding cable (G-3)
〔
Front view
〕
〔
Side view
〕
C N 20V
⑦
C N B
⑧
C N C
⑧
C N D
⑧
〔
Disconnect the black cable
〕
Screw
Square hole
Disconnect the white cable
Содержание SCM100ZJ-S1
Страница 64: ...63 11 SCM SM 110 Service data record form 55...
Страница 194: ...193 11 SCM SM 110 4 Ceiling cassette 4way compact type FDTC refer to page 157 to 172...
Страница 198: ...197 11 SCM SM 110 PJAO12D786...
Страница 223: ...222 11 SCM SM 110 4 way valve coil 1 Disconnect the connector 2 Loosen a screw and remove the coil Connector Screw Coil...
Страница 237: ...236 11 SCM SM 110 EEVB EEVC EEVA EEVD MARKING GREEN BLUE RED WHITE EEV A EEV D 46 WH 46 46 46 M YE OR BL RD Input 12VDC...