'11 • SCM-SM-110
0 rps
A rps or less
More than A rps, but B rps or less
More than B rps
Decision speed
0 rps
A rps
A rps to B rps
B rps
Indoor compressor command total speed value
Model
Item
A
B
30 rps
100 rps
SCM40ZJ-S
30 rps
120 rps
SCM45ZJ-S
30 rps
120 rps
SCM50ZJ-S1
Model
Item
A
SCM60ZJ-S1
B
Two connection
More than three connection
One connection
More than two connection
40 rps
30 rps
90 rps
120 rps
SCM71ZJ-S1
SCM80ZJ-S1
Model
Item
A
SCM100ZJ-S1
B
Three connection
More than fore connection
One connection
More than two connection
31 rps
31 rps
80 rps
SCM125ZJ-S1
Values of A, B
105 rps
110 rps
1.3 Outline of heating operation
(1) Summary
(a) Capacity control
1) Indoor unit SRK
**
ZJX models only
Model
Capacity
SCM40ZJ-S
1.4
̅
6.9 kW
SCM45ZJ-S
1.4
̅
7.4 kW
SCM125ZJ-S1
1.5
̅
14.0 kW
SCM50ZJ-S1
1.4
̅
7.5 kW
SCM60ZJ-S1
1.5
̅
7.8 kW
SCM71ZJ-S1
1.5
̅
9.4 kW
SCM80ZJ-S1
1.5
̅
9.8 kW
Model
Capacity
SCM100ZJ-S1
1.5
̅
13.5 kW
Capacity control is within the range shown above. If demand capacity of the indoor units exceeds the maximum capacity of
the outdoor unit, the demand capacity will be proportionally distributed.
(b) Outdoor compressor speed control
2) Indoor unit except SRK
**
ZJX models
Model
Capacity
SCM40ZJ-S
1.4
̅
6.7 kW
SCM45ZJ-S
1.4
̅
7.2 kW
SCM50ZJ-S1
1.4
̅
7.3 kW
SCM60ZJ-S1
1.5
̅
7.6 kW
SCM71ZJ-S1
1.5
̅
9.1 kW
SCM80ZJ-S1
1.5
̅
9.5 kW
Model
Capacity
SCM100ZJ-S1
1.5
̅
13.3 kW
SCM125ZJ-S1
1.5
̅
13.8 kW
(3) Hot keep operation
If the hot keep operation is selected during the heating operation, the indoor fan is controlled based on the temperature of the
indoor unit heat exchanger (Th) to prevent blowing of cool wind.
Note () Refer to the FDTC, FDEN and FDUM series by page.
Functional
components
Operation
Command speed
Indoor
unit fan
Compressor
Outdoor unit fan
Electronic
expansion valve
Multi-operation rpm calculated based
on the rpm required for each indoor unit
ON
According to command speed
According to outdoor unit speed
According to decision
speed
0
(All indoor units)
Hot Keep
OFF
According to stop mode
Hot Keep
Hot Keep
Hot Keep
0
(Thermostat off units)
ON
According to heating stop unit control
(Thermostat off units)
According to outdoor unit speed
According to mode switching
According to heating stop unit control
(Fan, stop, abnormal stop units)
0
(Fan, stop, abnormal stop units)
0
(All units)
ON
According to command speed
According to mode switching
OFF
OFF
OFF
According to stop mode
Heating
Thermostat OFF
(All indoor units)
Thermostat OFF
(Some of indoor units)
Fan, stop, abnormal stop
(Some of indoor units)
Failure
(Outdoor unit)
Fixed
Automatic
(2) Operation of major functional components in heating mode
Содержание SCM100ZJ-S1
Страница 64: ...63 11 SCM SM 110 Service data record form 55...
Страница 194: ...193 11 SCM SM 110 4 Ceiling cassette 4way compact type FDTC refer to page 157 to 172...
Страница 198: ...197 11 SCM SM 110 PJAO12D786...
Страница 223: ...222 11 SCM SM 110 4 way valve coil 1 Disconnect the connector 2 Loosen a screw and remove the coil Connector Screw Coil...
Страница 237: ...236 11 SCM SM 110 EEVB EEVC EEVA EEVD MARKING GREEN BLUE RED WHITE EEV A EEV D 46 WH 46 46 46 M YE OR BL RD Input 12VDC...