121
-
'11 • SCM-SM-110
Error code
Remote controller:
LED
Green
Red
Indoor
Content
E39
Discharge pipe
temperature sensor anomaly
Keeps flashing
Stays OFF
Outdoor
–
8
times flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is the
discharge pipe
temperature sensor
connector connected
properly?
YES
Are the
characteristics
of discharge pipe
temperature
sensor
OK?
NO
For the characteristics of discharge pipe
temperature sensor, see the following graph.
YES
140
120
100
80
60
40
20
0
0
100
50
[T 90
°C
]
NO
Temperature-resistance characteristics
Temperature sensor resistance (k
Ω
)
Temperature (°C)
(Broken wire)
(Shot circuit)
Correct connector.
Defective discharge pipe
temperature sensor
➞
Replace.
Defective outdoor main
(control) PCB
➞
Replace.
(Defective temperature
sensor input circuit)
2. Error detection method
Detection of anomalously low
temperature (resistance) on
the discharge pipe temperature
sensor
3. Condition of Error displayed
When the temperature sensor
detects -25 °C or lower for 5
seconds continuously within
10 minutes to 10 minutes 20
seconds after the compressor
ON, the compressor stops. After
3-minutes delay, the compressor
starts again automatically, but
if this anomalous temperature
is detected 3 times within 40
minutes.
4. Presumable cause
• Defective outdoor main
(control) PCB
• Broken sensor harness or
temperature sensing section
(Check molding.)
• Disconnected wire connection
(connector)
Note:
Содержание SCM100ZJ-S1
Страница 64: ...63 11 SCM SM 110 Service data record form 55...
Страница 194: ...193 11 SCM SM 110 4 Ceiling cassette 4way compact type FDTC refer to page 157 to 172...
Страница 198: ...197 11 SCM SM 110 PJAO12D786...
Страница 223: ...222 11 SCM SM 110 4 way valve coil 1 Disconnect the connector 2 Loosen a screw and remove the coil Connector Screw Coil...
Страница 237: ...236 11 SCM SM 110 EEVB EEVC EEVA EEVD MARKING GREEN BLUE RED WHITE EEV A EEV D 46 WH 46 46 46 M YE OR BL RD Input 12VDC...