'11 • SCM-SM-110
(9) Air outlet selection (SRF series only)
(a) AIR SELECTION button can switch between the combination of upper and lower air outlets and upper air
outlet. Not operable while the air conditioner is OFF.
1) Each time the AIR SELECTION button is pressed. The combination of the
upper and lower air outlets and the upper air outlet can be switched.
2) When the upper air outlet is selected, AIR OUTLET SELECTION light on
the unit display area will light green.
AIR OUTLET SELECTION
light : OFF
AIR OUTLET SELECTION
light : ON
Upper air outlet
Upper and lower air outlets
AIR SELECTION button
(b) Auto air outlet selection
1) COOL, DRY operation
a) In case both lower and upper outlets operation is selected in Cooling or Dry
operation, both outlets will be kept for sixty minutes after the start or until
indoor temperature is below the setting point. And then the air outlet will change
to the upper outlet. That state will be maintained until switch is turned off.
b) In case both outlets operation with Auto fan speed mode is selected, the upper
outlet will be kept for ten minutes after the start or until indoor temperature is
close to reaching the setting point . And then the air outlet will change to both
outlets in order to spread comfort air to every corner.
2) HEAT operation
a) In case both lower and upper outlets operation with Auto fan speed mode is
selected, the lower outlet will be kept for twenty minutes after the start or until
indoor temperature is close to reaching the setting point . And then the air outlet will
change to both outlets. That state will be maintained until the switch is turned off.
b) Automatic adjustment of lower air outlet direction prevents stirring up of
warm air and keeps optimum comfort at floor level.
(10) 3D auto operation (SRK series only)
(Except SRK71ZK-S model)
Control the flap and louver by D AUTO button on the wireless remote controller.
Air flow selection and air flow direction are automatically controlled, allowing the entire indoor to efficiently conditioned.
(a)
During Cooling and Heating (Including auto cooling and heating)
1)
Air flow selection is determined according to indoor temperature and setting temperature.
At cooling
Air flow selection
Operation mode
AUTO
HI
MED
LO
At heating
Indoor temp. – Setting temp. >5°C
Indoor temp. – Setting temp. 5°C
Setting temp. – Indoor temp. >5°C
Setting temp. – Indoor temp. 5°C
HIGH POWER
AUTO
HI
MED
LO
HIGH POWER
AUTO
<
=
<
=
Содержание SCM100ZJ-S1
Страница 64: ...63 11 SCM SM 110 Service data record form 55...
Страница 194: ...193 11 SCM SM 110 4 Ceiling cassette 4way compact type FDTC refer to page 157 to 172...
Страница 198: ...197 11 SCM SM 110 PJAO12D786...
Страница 223: ...222 11 SCM SM 110 4 way valve coil 1 Disconnect the connector 2 Loosen a screw and remove the coil Connector Screw Coil...
Страница 237: ...236 11 SCM SM 110 EEVB EEVC EEVA EEVD MARKING GREEN BLUE RED WHITE EEV A EEV D 46 WH 46 46 46 M YE OR BL RD Input 12VDC...