187
-
'11 • SCM-SM-110
Keep the openings of the pipes covered with tapes etc. to prevent dust, sand, etc.
from entering them.
Secure using upper 2 screws for floor installations.
If possible, also attach two lower screws.
At first secure the installation board using 5 screws and the indoor unit using 2 screws.
(860)
103.5
726
30.5
25.5
58
5
5
58
5
59
5
(6
00
)
30.5
(23
8)
19
8
18
5
If there is an obstacle such as a cable cover,
cut off the hatched part before installation.
Installation of Installation board
Look for the inside wall structures (Intersediats
support or pillar and finally install the unit after level
surface has been checked.)
Fixing on concrete wall
Use of nut anchor
Installation
board
Bolt
(M6 12)
Adjustment of the installation board in the horizontal
direction is to be conducted with five screws in a temporary
tightened state.
When practicing the half-console, make sure to fix the unit securely.
Adjust so the board will be level by turning the board with
the standard hole as the center.
Standard hole
Latch
Latch
155
45
105
130
140
Otherwise, it could fall.
CONNECTION OF REFRIGERANT PIPINGS
ELECTRICAL WIRING WORK
Preparation
Indoor
(Do not turn)
Press
Remove
A
90 ± 0.5°
Dimension A
Liquid side ø6.35:9.1(mm)
Gas side ø9.52:13.2(mm)
ø12.7:16.6(mm)
Remove the flared nuts. (on both liquid and gas sides)
Install the removed flared nuts to the pipes to
be connected,then flared the pipes.
CAUTION
Do not apply refrigerating machine oil to the flared surface.
CAUTION
In case of faulty wiring connection, the indoor unit
stops, and then the run lamp turns on and the timer
lamp blinks.
CAUTION
During installation, do not lean on the control box or the display, as they
may be damaged.
Pass the connecting wire securely through the wiring holder. If it passes
on the sensor, it may not detect suction temperature and/or humidity.
Use cables for interconnection wiring to avoid
loosening of the wires.
CENELEC code for cables Required field cables.
H05RNR4G1.5 (example) or 245IEC57
H Harmonized cable type
05 300/500 volts
R Natural-and/or synth, rubber wire insulation
N
Polychloroprene rubber conductors insulation
R Stranded core
4or5 Number of conductors
G One conductor of the cable is the earth
conductor (yellow/green)
1.5 Section of copper wire (mm
2
)
Flaring work
Measurement B
Flaring
block
Copper pipe
Copper pipe diameter
Use a flare tool designed for R410A or a conventional flare tool.
Please note that measurement B (protrusion from the flaring block) will vary depending
on the type of a flare tool in use.
If a coventional flare tool is used, please use a copper pipe gauge or a similar
instrument to check protrusion so that you can keep measurement B to a correct value.
Clutch type flare tool for
R410A
Conventional (R22) flare tool
ø6.35
ø9.52
ø12.7
0.0 - 0.5
0.0 - 0.5
0.0 - 0.5
1.0 - 1.5
1.0 - 1.5
1.0 - 1.5
1.5 - 2.0
1.5 - 2.0
2.0 - 2.5
Measurement B (mm)
Clutch type
Wing nut type
CAUTION
Do not apply excess torque to the flared nuts. Otherwise, the flared nuts may check depending.
CAUTION
(Do not pull with a force of larger than 5 kgf.)
Be careful not to stress the connecting refrigerant pipes.
Connection
How to fit the front panel
Close and attachment of the air inler panel
Insulation of the connection portion
Indoor
Liquid side
Gas side
(Do not turn)
Pass the refrigerant pipe through the piping hole to
indoor side.
Arrange the pipes according to the direction of piping.
Cover the coupling with insulator and then cover it with tapes.
Position it so that the slit area faces upward.
Connect the pipes on both liquid and gas sides.
Tighten the nuts to the following torque.
Liquid side (ø6.35) : 14.0 - 18.0 N·m (1.4 - 1.8 kgf·m)
Gas side (ø9.52) : 34.0 - 42.0 N·m (3.4 - 4.2 kgf·m)
(ø12.7) : 49.0 - 61.0 N·m (4.9 - 6.1 kgf·m)
Finishing work and fixing
Connection wiring,
Earth wiring
Outer tape
Refrigerant piping
Drain hose
Wood screw
Clamp
Cover the exterior portion with outer tape
and shape the piping so it will match the
contours of the route that the piping to take.
Also fix the wiring and pipings to the wall
with clamps.
Fitting
1
Do remove the air filter.
2
Cover the body with the front panel.
3
Fit the 6 latches in the lower section.
then 3 latches in the upper section.
4
Tighten the 5 set screws.
5
Fit the air filter.
6
Fit the air inlet panel.
To close, attach the panel after pulling
the strings, hold the panel at both ends of
upper part to lower downward and push it
slightly until the latch works.
Preparation of indoor unit
1
Remove the fixing screw of clamp.
2
Connect the connecting wire securely to the terminal block.
1 ) Connect the connection wire securely to the terminal
block. If the wire is not affixed completely, contact will be
poor, and it is dangerous as the terminal block may heat
up and catch fire.
2 ) Take care not to confuse the terminal numbers for indoor
and outdoor connections.
3
Fix the connecting wire by wiring clamp.
4 Pass the connecting wire through the wiring holder.
Mounting of connecting wires
Fixing of indoor unit
Floor installation
Wall installation
・
During the installation, do not lean on the control box or the display, as they may be damaged.
・
Install the indoor unit on flat wall. If improperly installed, it may cause abnormal noise and vibration. (Distortion on the wall shall be no larger than 3 mm.)
CAUTION
Tapping screw
Use an attached pipe cover for heat insulation.
Refrigerant
pipe
Slit
Refrigerant
pipe
Slit
Tape
Add
⑩
band
Refrigerant
pipe
⑨
Pipe cover
CAUTION
If heat insulation is insufficient, water leakage
may occur. In addition, the room temperature
sensor may give a false alert due to heat
radiation from the pipes.
Cover the indoor unit’s flare-connected joints, after
they are checked for a gas leak, with an indoor unit
heat insulating material and then wrap them with a
tape with an attached pipe cover placed over the
heat insulating material’s slit area.
(860)
103.5
156.5
726
585
5
585 595
(600)
30.5
83.5
(238)
Terminal block
Sensor
Fixing screw
Clamp
Wiring holder
Содержание SCM100ZJ-S1
Страница 64: ...63 11 SCM SM 110 Service data record form 55...
Страница 194: ...193 11 SCM SM 110 4 Ceiling cassette 4way compact type FDTC refer to page 157 to 172...
Страница 198: ...197 11 SCM SM 110 PJAO12D786...
Страница 223: ...222 11 SCM SM 110 4 way valve coil 1 Disconnect the connector 2 Loosen a screw and remove the coil Connector Screw Coil...
Страница 237: ...236 11 SCM SM 110 EEVB EEVC EEVA EEVD MARKING GREEN BLUE RED WHITE EEV A EEV D 46 WH 46 46 46 M YE OR BL RD Input 12VDC...