135
-
'11 • SCM-SM-110
Error code
Remote controller:
LED
Green
Red
Content
Indoor Keeps flashing Stays OFF
E59
Compressor startup failure
Outdoor
–
2
times flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
NO
Is power
supply voltage
OK?
Is
the pressure balance
at starting OK?
NO
NO
Is the
insulation resistance
and coil resistance of
compressor OK ?
Is power transistor
module OK?
Try to startup
several times
Does it start?
NO
NO
Is
the output of inverter
checker OK ?
Compressor does not start at all.
Neither noise nor vibration cannot be heard
Disconnect the outdoor fan motor
connector and try to startup
Does
compressor
startup?
YES
Note: Several times restarting
may resolve it, because migrated
liquid refrigerant in the
compresser is discharged from
the compressor.
YES
YES
YES
YES
YES
NO
Replace outdoor fan motor
Check power supply
voltage
Check refrigerant amount
and refrigerant circuit
Repalce compressor
Defective outdoor main
PCB
➞
Replace
Defective outdoor main
PCB
➞
Replace
Repalce compressor
2. Error detection method
If it fails to change over to the
rotor detection operation of
compressor motor
3. Condition of Error displayed
If compressor fails to startup for
42 times
4. Presumable cause
• Faulty outdoor fan motor
• Faulty outdoor main PCB
• Anomalous power supply
voltage
• Improper refrigerant amount
and refrigerant circuit
• Faulty compressor (Motor
bearing)
Note: Insulation resistance
•
The unit is left for long period without power supply or soon after installation, migrated liquid refrigerant may dissolve in the refrigerant oil in the compressor.
In such case insulation resistance decreases upto several M
Ω
or lower. If the electric leakage breaker is activated due to low insulation resistance,
check followings.
➀
Check whether the electric leakage breake conforms to high-hermonic specifications
(As units has inverter, in order to prevent from improper operation, be sure to use high-hermonic one.)
Содержание SCM100ZJ-S1
Страница 64: ...63 11 SCM SM 110 Service data record form 55...
Страница 194: ...193 11 SCM SM 110 4 Ceiling cassette 4way compact type FDTC refer to page 157 to 172...
Страница 198: ...197 11 SCM SM 110 PJAO12D786...
Страница 223: ...222 11 SCM SM 110 4 way valve coil 1 Disconnect the connector 2 Loosen a screw and remove the coil Connector Screw Coil...
Страница 237: ...236 11 SCM SM 110 EEVB EEVC EEVA EEVD MARKING GREEN BLUE RED WHITE EEV A EEV D 46 WH 46 46 46 M YE OR BL RD Input 12VDC...