108
-
'11 • SCM-SM-110
Error code
Remote controller:
LED
Green
Red
Indoor
Content
E7
Return air temperature
thermistor anomaly
Keeps flashing 1 time flash
Outdoor
–
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
NO
YES
Is the
connection of return
air temperature thermistor
connector OK?
Are the
characteristics of return air
temperature thermistor
OK?
YES
15
10
5
0
10
30
40
20
50
Temperature-resistance characteristic
Te
mperature thermistor resistance (k
Ω
)
Temperature (°C)
5k
Ω
at 25
°C
(Broken wire)
(Shot circuit)
Correct.
➞
Connect
connector.
Defective return air
temperature thermistor
➞
Replace.
Defective indoor control
PCB
➞
Replace.
(Defective return air
temperature thermistor
input circuit)
2. Error detection method
Anomalously low temperature
or high temperature (resistance)
is detected by indoor return air
temperature thermistor (ThI-A)
3. Condition of Error displayed
• When the temperature thermistor
detects -20°C or lower for
5 seconds continuously, the
compressor stops. After 3-minute
delay, the compressor starts again
automatically, but if this error
occurs again within 60 minutes
after the initial detection.
4. Presumable cause
• Defective return air
temperature thermistor
connector
• Defective return air
temperature thermistor
• Faulty indoor control PCB
Note:
Содержание SCM100ZJ-S1
Страница 64: ...63 11 SCM SM 110 Service data record form 55...
Страница 194: ...193 11 SCM SM 110 4 Ceiling cassette 4way compact type FDTC refer to page 157 to 172...
Страница 198: ...197 11 SCM SM 110 PJAO12D786...
Страница 223: ...222 11 SCM SM 110 4 way valve coil 1 Disconnect the connector 2 Loosen a screw and remove the coil Connector Screw Coil...
Страница 237: ...236 11 SCM SM 110 EEVB EEVC EEVA EEVD MARKING GREEN BLUE RED WHITE EEV A EEV D 46 WH 46 46 46 M YE OR BL RD Input 12VDC...