117
-
'11 • SCM-SM-110
Error code
Remote controller:
LED
Green
Red
Content
Indoor
Stays OFF
Keeps flashing
E35
Outdoor
–
2
times flash
1. Applicable model
5. Troubleshooting
Model SCM100, 125 only
Diagnosis
Countermeasure
Are normal
the characteristics of
high pressure sensor
normal?
Is
the pressure
(measured actually) at
direction of error
correct?
NO
YES
YES
Is the
unit operating in
the state of cooling
overload?
Is the high
pressure control
normal
YES
YES
* For the characteristics of
high pressure sensor, refer to E54.
NO
NO
NO
Replace high pressure
sensor.
Check unit side.
• Isn’t the air circulation
of outdoor unit short-
circuited?
• Are installation spaces
adequate?
• Isn’t there any fouling
or clogging on heater
exchanger?
Control operation check*
Defective outdoor control
PCB
➞
Replace.
Excessive refrigerant
amount: Recharge
refrigerant by weighing
proper amount on a scale.
2. Error detection method
For the error detection method,
refer to the protective control by
controlling compressor rotation
speed and cooling high pressure
protective control of micro
computer control function for
corresponding models.
(
Refer to 41 page
)
3. Condition of Error displayed
•
When anomalous rise of
the high pressure sensor is
detected 5 times within 1 hour.
•
When high pressure sensor
anomaly is detected for 10
minutes continuously.
4. Presumable cause
• Defective high pressure sensor
• Defective outdoor control PCB
• Indoor, outdoor unit
installation spaces
• Short-circuit of air on indoor,
outdoor units
• Fouling, clogging of heat
exchanger
• Excessive refrigerant quantity
Note:
Cooling
high pressure
operation
(
Model SCM100
,
125
)
Содержание SCM100ZJ-S1
Страница 64: ...63 11 SCM SM 110 Service data record form 55...
Страница 194: ...193 11 SCM SM 110 4 Ceiling cassette 4way compact type FDTC refer to page 157 to 172...
Страница 198: ...197 11 SCM SM 110 PJAO12D786...
Страница 223: ...222 11 SCM SM 110 4 way valve coil 1 Disconnect the connector 2 Loosen a screw and remove the coil Connector Screw Coil...
Страница 237: ...236 11 SCM SM 110 EEVB EEVC EEVA EEVD MARKING GREEN BLUE RED WHITE EEV A EEV D 46 WH 46 46 46 M YE OR BL RD Input 12VDC...